It is a screen for other signal relay setting the 2
nd
screen.
①
It sets the ascending, descending signal relay and operation deviation.
☞
The state lamp of the operation screen and relay is operated at the same time.
☞
In case of program operation
The relay is on till [Tartest setting data (TSP) – Setting temperature (Deviation)].
②
It sets the holding signal relay and holding time.
☞
In case of stationary operation → The state lamp is in operation screen, but the relay output is not
created.
☞
In case of program operation
The state lamp and relay on the operation screen are ‘ON’ during [Holding range operation time
(SEG TIME) – Setting temperature (Holding time)].
③
It sets the relay and delay time of the 1
st
, 2
nd
refrigerator operation signal.
④
It sets the error signal relay and holding time.
☞
The error is occurred during stop and operation, the set relay is “ON.”
☞
The relay holds the “ON” state during setting time and it is “OFF” after holding time.
☞
The relay keeps “ON” state when the error is not recovered during holding time and relay is “OFF” at
the error recovery time.
Table 13-9.
Other signal relay setting the 2
nd
screen
Parameter
Parameter
Setting range
Unit
Initial data
Ascending signal relay
0~32
ABS
0
Ascending relay application deviation
EUS(0.0~10.0%)
EUS
EUS(0.0%)
Holding signal relay
0~32
ABS
0
Holding signal holding time
00.00~99.59 (MIN.SEC)
ABS
00.00
Descending signal relay
0~32
ABS
0
Descending relay application deviation
EUS(0.0~10.0%)
EUS
EUS(0.0%)
Freezer signal 1.REF relay
0~32
ABS
0
Freezer signal 1.REF relay
delay time
00.00~99.59 (MIN.SEC)
ABS
00.00
Freezer signal 2.REF relay
0~32
ABS
0
Freezer signal 2.REF relay
delay time
00.00~99.59 (MIN.SEC)
ABS
00.00
Error signal relay
0~32
ABS
0
[Fig. 13-8] Other signal relay setting the 2
nd
screen
②
③
④
①