2nd Edition of TEMP2000M_Series IM : April. 8. 2014 Page 21 / 176
1.3.3.3 3 Output (Relay) wiring for external connection point
▶
Please switch off the electric power and power supply to outside from the TEMP2000M main body
certainly in case of wiring the external contact point output because there is an electric shock risk.
▶
Connecting point output (RELAY) : NORMAL OPEN under 30VDC 1A, under 250VAC 1A
Under 30V DC 1A, under 250V AC 1A
Under 30V DC 1A, under 250V AC 1A
Under 30V DC 1A, under 250V AC 1A
NO(NORMAL OPEN): Under 30V DC 1A, Under 250V AC 1A
NC(NORMAL CLOSE):Under 30V DC 1A, Under 250V AC
1A
1.3.3.4 Input wiring for contact point (DI)
▶
Use the dry contact point for the external connection point (Relay contact point).
▶
Use the dry contact with sufficient opening and closing capacity for the terminal voltage (About 5V) in
case of OFF and electric current (About 1mA) in case of ON.
▶
Use the both terminal voltage under 2V, and under 100μA of leak current in case of contact point ON
when the open collector is used.
Relay contact point input
Transistor contact point input
I/O1 BOARD
I/O2 BOARD
RLY1
•
•
•
COM
RLY2
COM
RLY13
•
•
•
COM
RLY14
COM
I/O1 BOARD
I/O1 BOARD
RLY9_NC
RLY9_NO
COM
RLY10_NC
RLY10_NO
RLY11_NC
RLY11_NO
COM
RLY12_NC
RLY12_NO
I/O1 BOARD
I/O1 BOARD
DI1
DI2
DI16
DI_COM
•
•
•
DI1
DI2
DI16
DI_COM
•
•
•