2nd Edition of TEMP2000M_Series IM : April. 8. 2014 Page 93 / 176
11.1.2 Sensor input the 2
nd
screen
▶
It calibrates the temperature range input.
▶
The range calibration is applied in the form of the equation of the first between the calibration points.
①
It sets the input calibration of the temperature.
②
It sets the temperature at each basic point for temperature calibration.
③
It sets the calibration temperature at each basic temperature.
④
It displays the input calibration adopted temperature.
☞
The change by touching is impossible as it is only for reading.
Table 11-2. Sensor input parameter calibration screen for each range
Parameter
Setting range
Unit
Initial data
Input calibration 1 data
Input calibration 2 data
Input calibration 3 data
Input calibration 4 data
Input calibration 5 data
Input calibration 6 data
Input calibration 7 data
Input calibration 8 data
EUS(-10.0 ~ 10.0%)
EUS
EUS(0.0%)
EU(0.0%)
EU(100.0%)
EU(100.0%)
EU(100.0%)
EU(100.0%)
EU(100.0%)
EU(100.0%)
Input calibration 1 point
Input calibration 2 point
Input calibration 3 point
Input calibration 4 point
Input calibration 5 point
Input calibration 6 point
Input calibration 7 point
Input calibration 8 point
EU(0.0 ~ 100.0%)
PV of Lower limit range
≤ PV of Input calibration1 point
≤ PV of Input calibration2 point
≤ PV of Input calibration3 point
≤ PV of Input calibration4 point
≤ PV of Input calibration5 point
≤ PV of Input calibration6 point
≤ PV of Input calibration7 point
≤ PV of Input calibration8 point
≤ PV of Upper limit range
EU
EU(100.0%)
[Fig. 11-10] Sensor input calibration screen for each range
①
②
③
④