2nd Edition of TEMP2000M_Series IM : April. 8. 2014 Page 44 / 176
3.4.2 Auto tuning (Zone PID type)
▶
The tuning is made with the target of the center point of boundary data in PID No. group set in auto
tuning parameter and the tuning data is saved into the set PID No.
▶
The current setting data is changed into the auto tuning setting data when the auto tuning is performed.
☞
The SEG is held during program operation.
▶
The current setting data is changed into previous setting data during auto tuning termination.
☞
The SEG is processed during program operation.
▶
The auto tuning data is not saved into PID No. when it is forcibly released during automatic auto tuning.
☞
The tuning data is not saved into the PID No during automatic auto tuning when in case of blackout.
①
The tuning data is saved with selected PID No. at the completion of auto tuning.
☞
The figures inside the box display the PID No.
☞
When the auto is selected, the tuning data is save sequentially in 1 ~ 6.
Table 3-4 Auto tuning (Zone) parameter
Parameter
Setting range
Unit
Initial value
AUTO TUNING
OFF, 1 ~ 6, Auto
ABS
OFF
Cautions in auto tuning (Zone type)
▶
Even single PID No. is not saved when the Auto tuning is forcibly terminated. .
▶
Even single PID No. is not saved in case of blackout.
[Fig. 3-18] Zone PID auto tuning screen
①