Saia-Burgess
Controls Ltd.
Hardware Manual for the PCD3 Series│Document 26/789; Version E 5│31.01.2005
Hardware
PCD3.A200
5-30
5
5.3.1 PCD3.A200, 4 relay contacts, type “NO”, with contact protection
Application
The module contains 4 relays with normally-open contacts for direct or alternating
current up to 2 A, 250 VAC.The relay contacts are protected by a varistor and an RC
element. The module is especially suited wherever perfectly isolated AC switching
circuits must be controlled with infrequent switching.
Technical data
Number of outputs:
4, electrically isolated NO contacts
Type of relay (typical):
RE 030024, SCHRACK
Switching rating:
(contact lifetime)
2A, 250 VAC AC1
0,7 x 10
6
operations
1 A, 250 VAC AC11
1,0 x 10
6
operations
2 A, 50 VDC DC1
0,3 x 10
6
operations
3)
1 A, 24 VDC DC11
0,1 x 10
6
operations
1)3)
Relay coil supply:
2)
nominal 24 VDC smoothed or pulsed,
8 mA per relay
Voltage tolerance:
Dependent on Ambient temperature
20°C: 17.0...35 VDC
30°C: 19.5...35 VDC
40°C: 20.5...32 VDC
50°C: 21.5...30 VDC
Typical output delay:
5 ms at 24 VDC
Resistance to interference:
according to IEC 801-4
4 kV under direct coupling
2 kV under capacitive coupling (whole trunk group)
Internal current consumption:
(from +5 V bus)
1...15 mA
typ. 10 mA
Internal current consumption:
(from V+ bus)
0 mA
External current consumption:
max. 32 mA
Terminal:
Pluggable 10-pole cage clamp terminal (4 405 4957 0)
or pluggable 10-pole screw terminal (4 405 4959 0),
both for wires up to 2.5 mm²
1)
With external protective diode
2)
With reverse voltage protection
3)
These ratings are not UL-listed!