Saia-Burgess
Controls Ltd.
Hardware Manual for the PCD3 Series│Document 26/789; Version E 5│31.01.2005
Hardware
PCD3.W3x5
5-51
5
Connection terminals
Digital-/analogue values
Input signals and type
Digital values
PCD3.W305
PCD3.W315
PCD3.W325
Classic xx7
Simatic
+ 10.0 V
+ 20 mA
+10 V
4095
4095
27684
+ 5.0 V
+ 10 mA
0 V
2047
2047
13824
0 V
0 mA
-10 V
0
0
0
Connection concept for voltage and current inputs
The voltage and current input signals are connected directly to the 14-pole cage
clamp terminal (E0 … E6 and COM). To minimize the amount of noise coupled into
the module via the transmission lines, connection should be made according to the
principle explained below.
The following connection diagram shows a typical wiring layout for:
●
voltage inputs with the PCD3.W305 and PCD3.W325 modules or
current inputs with the PCD3.W315
●
If screened cables are used, screening should be continued to an external
earthing bar
0
1
2
3
4
5
6
7
Description-
label
Address-
label
Terminal 13
0
1
2
3
4
5
6
7
8
9
10
11
12
13
PCD3.W305 A 7
input
s
0-10V
Galvanic
Sep
arated
W
3
0
5
E0
GND
E1
GND
E2
GND
E3
GND
E4
GND
E5
GND
E6
GND
0
1
2
3
4
5
6
7
8
9
10
11
12
13
PCD3.W315 A 7
input
s
0-20mA
Galvanic
Sep
arated
W
3
1
5
E0
GND
E1
GND
E2
GND
E3
GND
E4
GND
E5
GND
E6
GND
0
1
2
3
4
5
6
7
8
9
10
11
12
13
PCD3.W325 A 7
input
s
+
/-10V
Galvanic
Sep
arated
W
3
2
5
E0
GND
E1
GND
E2
GND
E3
GND
E4
GND
E5
GND
E6
GND
Terminal 0
Terminals