5.3.3 PCD3.A220, 6 relay contacts, type “NO”, w/o contact protection
Application
The module contains 6 relays with normally-open contacts for direct or alternating
current up to 2 A, 250 VAC. It is especially suited wherever perfectly isolated AC
switching circuits must be controlled with infrequent switching. On this module there
is no contact protection available. There are two groups of three relay contacts, which
have one common terminal (see output diagram).
Technical data
Number of outputs:
3 + 3, NO contacts with common terminal
Type of relay (typical):
RE 030024, SCHRACK
Switching rating:
(contact lifetime)
2 A, 250 VAC AC1
0,7 x 10
6
operations
1 A, 250 VAC AC11
1,0 x 10
6
operations
2 A, 50 VDC DC1
0,3 x 10
6
operations
3
)
1 A, 24 VDC DC11
0,1 x 10
6
operations
1
),
3
)
Relay coil supply:
2
)
nominal 24 VDC smoothed or pulsed, 8 mA per relay
Voltage tolerance:
dependent on
ambient temperature
20°C: 17.0...35 VDC
30°C: 19.5...35 VDC
40°C: 20.5...32 VDC
50°C: 21.5...30 VDC
Typical output delay:
5 ms at 24 VDC
Resistance to interference:
according to IEC 801-4
4 kV under direct coupling
2 kV under capacitive coupling (whole trunk group)
Internal current consumption:
from +5 V bus
1...20 mA
typ. 10 mA
Internal current consumption:
(from V+ bus)
0 mA
External current consumption:
max. 48 mA
Terminal:
Pluggable 10-pole cage clamp terminal (4 405 4957 0) or
pluggable 10-pole screw terminal (4 405 4959 0), both for
wires up to 2.5 mm²
1
) With external protective diode
2
) With reverse voltage protection