5.4.1 PCD3.W2x0, analogue inputs, 8 channels, 10 bit resolution
Application
With its short conversion time of <50 µs, this module is universally suitable for
recording analogue signals. The modules are not suitable for low resistance
measurements like Pt 100, nor for thermocouples.
Module overview
PCD3.W200
8 channels for signals 0...10V
PCD3.W210
8 channels for signals 0...20 mA
PCD3.W220
8 channels for resistive temperature sensors Pt/Ni 1000,
other types of temperature sensors with resistances up to 2.5 kΩ
can be connected
Technical data
Input ranges:
see above
Module overview
Galvanic separation:
no
Resolution (digital representa-
tion):
10 bits (0...1023)
Measuring principle:
non-differential, single ended
Input resistance:
0...10 V:
200 kΩ / 0.15%
0...20 mA:
125 Ω / 0,1%
Pt/Ni 1000:
see terminal contacts
Accuracy (referring to measured
value):
± 3 LSB
Repeating accuracy:
(under same conditions)
within 1 LSB
Temperature error (Across tem-
perature range 0°...+55°C):
± 0,3% ( ± 3 LSB)
Conversion time A/D:
<
50 μs
Overvoltage protection:
W200/220:
± 50 VDC
Overcurrent protection:
W210:
± 40 mA
Fast transient (Burst):
according to IEC 1000-4-4
± 1 kV, with unshielded cables
± 2 kV, with shielded cables
Time constant of input filter:
W200: typ. 5 ms
W210: typ. 1 ms
W220 : typ. 10 ms
Internal current consumption:
(from +5 V bus)
8 mA (W200/210/220)
Internal current consumption:
(from V+ bus)
5 mA (W200/210)
16 mA (W220)
External current consumption:
0 mA
Terminal:
Pluggable 10-pole cage clamp terminal (4 405 4957 0) or
pluggable 10-pole screw terminal (4 405 4959 0), both for
wires up to 2.5 mm²