Purge
This function provides a means of starting the drive at a preset
speed (Purge Speed) regardless of the selected control source.
The drive is typically configured for level-sense control
(LevelSense Start = Enabled) when using this function.
Purge supersedes the OIM Control function as well as any other
control command to take control of the drive. Purge can occur,
and is operational, at any time whether the drive is running or
stopped regardless of the selected logic source selection. Note
that if any start inhibit condition is present, the drive will not start
on the purge input transition.
Type 2 Alarms
Some digital input programming may cause conflicts that result
in a Type 2 alarm. Type 2 alarm prevent the drive from starting.
For example 361 [Digital In1 Sel] set to option 5 “Start” in 3-wire
control and 362 [Digital In2 Sel] set to option 7 “Run” in 2-wire
control. Refer to
for more information on alarms.
Di
gi
ta
l Out
put
s
380
384
[Digital Out1 Sel]
[Digital Out2 Sel]
Selects the drive status that will energize
a (CRx) output relay.
(1)
Any relay programmed as Fault or
Alarm will energize (pick up) when
power is applied to drive and
deenergize (drop out) when a fault or
alarm exists. Relays selected for other
functions will energize only when that
condition exists and will deenergize
when condition is removed. Refer to
page
(2)
Activation level is defined in [Dig Outx
Level] below.
Default:
Options:
1
4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
“Fault”
“Run”
“Fault”
(1)
“Alarm”
(1)
“Ready”
“Run”
“Forward Run”
“Reverse Run”
“Auto Restart”
“Reserved”
“At Speed”
“At Freq”
(2)
“At Current”
(2)
“At Torque”
(2)
“At Temp”
(2)
“At Bus Volts”
(2)
“At PI Error”
(2)
“DC Braking”
“Curr Limit”
“Economize”
“Motor Overld”
“Power Loss”
“Input 1 Link”
“Input 2 Link”
“Input 3 Link”
“Input 4 Link”
“Input 5 Link”
“Input 6 Link”
“TB in Manual”
002
001
003
004
218
012
137
157
147
053
048
184
F
ile
Gr
oup
No
.
Parameter Name and Description
See
page 3-2
for symbol descriptions
Values
Re
lated
Summary of Contents for 9VT201-007HTNNN
Page 1: ...VTAC 9 AC Drive Firmware Version 3 xx User Manual ...
Page 4: ...soc 2 ...
Page 14: ...P 8 Overview Publication 9VT UM001D EN P Notes ...
Page 56: ...1 42 Installation Wiring Publication 9VT UM001D EN P Notes ...
Page 62: ...2 6 Start Up Publication 9VT UM001D EN P Notes ...
Page 130: ...3 68 Programming and Parameters Publication 9VT UM001D EN P Notes ...
Page 150: ...4 20 Troubleshooting Publication 9VT UM001D EN P Notes ...
Page 176: ...A 26 Supplemental Drive Information Publication 9VT UM001D EN P Notes ...
Page 196: ...B 20 Using the LCD OIM Publication 9VT UM001D EN P Notes ...
Page 212: ...C 16 Application Notes Publication 9VT UM001D EN P Notes ...
Page 223: ......