Programming and Parameters
3-65
INPU
TS &
OUT
PUTS
Di
gi
tal
Outp
uts
Cont.
380
384
Option Descriptions
Fault
A fault has occurred and stopped the drive.
Alarm
A Type 1 or Type 2 alarm condition exists.
Ready
Drive is powered, enabled, and no start inhibits exist.
Run
Outputting voltage and frequency to motor (indicates 3-wire
control, either direction).
Forward Run
Outputting voltage and frequency to motor (indicates 2-wire
control in forward).
Reverse Run
Outputting voltage and frequency to motor (indicates 2-wire
control in reverse).
Auto Restart
Executing an “Auto Restart” or “Run at Power Up”.
At Speed
Commanded speed equals or exceeds programmed limit.
At Freq
Output frequency equals or exceeds programmed limit.
At Current
Total output current exceeds programmed limit.
At Torque
Output torque current component exceeds programmed limit.
At Temp
Operating temperature exceeds programmed limit.
At Bus Volts
Bus voltage exceeds programmed limit.
At PI Error
Process PI Loop error exceeds programmed limit.
DC Braking
Executing a “DC Brake” or “Ramp to Hold” and DC braking
voltage is being applied to motor.
Curr Limit
Drive is limiting output current.
Economize
Drive is eliminating excess output voltage.
Motor Overld
Drive is eliminating excess output voltage.
Power Loss
Detected loss of AC input power that caused DC bus voltage to
fall below fixed limit.
Input x Link
Digital input value outputting on [Dig Outx Level].
TB in Manual
Terminal block has manual reference control.
381
385
[Dig Out1 Level]
[Dig Out2 Level]
Sets the relay activation level for options
10 – 15 in [Digital Outx Sel]. Units are
assumed to match the above selection
(i.e. “At Freq” = Hz, “At Torque” = Amps).
Default:
Min/Max:
Units:
0.0
0.0
0.0/819.2
0.1
382
386
[Dig Out1 OnTime]
[Dig Out2 OnTime]
Sets the “ON Delay” time for the digital
outputs. This is the time between the
occurrence of a condition and activation of
the relay.
Default:
Min/Max:
Units:
0.00 Secs
0.00 Secs
0.00/600.00 Secs
0.01 Secs
383
387
[Dig Out1 OffTime]
[Dig Out2 OffTime]
Sets the “OFF Delay” time for the digital
outputs. This is the time between the
disappearance of a condition and
de-activation of the relay.
Default:
Min/Max:
Units:
0.00 Secs
0.00 Secs
0.00/600.00 Secs
0.01 Secs
F
ile
Gr
oup
No
.
Parameter Name and Description
See
page 3-2
for symbol descriptions
Values
Re
lated
Summary of Contents for 9VT201-007HTNNN
Page 1: ...VTAC 9 AC Drive Firmware Version 3 xx User Manual ...
Page 4: ...soc 2 ...
Page 14: ...P 8 Overview Publication 9VT UM001D EN P Notes ...
Page 56: ...1 42 Installation Wiring Publication 9VT UM001D EN P Notes ...
Page 62: ...2 6 Start Up Publication 9VT UM001D EN P Notes ...
Page 130: ...3 68 Programming and Parameters Publication 9VT UM001D EN P Notes ...
Page 150: ...4 20 Troubleshooting Publication 9VT UM001D EN P Notes ...
Page 176: ...A 26 Supplemental Drive Information Publication 9VT UM001D EN P Notes ...
Page 196: ...B 20 Using the LCD OIM Publication 9VT UM001D EN P Notes ...
Page 212: ...C 16 Application Notes Publication 9VT UM001D EN P Notes ...
Page 223: ......