Installation/Wiring
1-41
Table 1.O Maximum Motor Cable Length for FCC Compliance Note: Use of these
filters assumes that the drive is mounted in an EMC enclosure.t
Frame
HP @
480V
Restrict
Motor Cable
to:
External
Filter
Required
Common
Mode Core
Required
Restrict
Motor Cable
to:
External
Filter
Required
Common
Mode Core
Required
B
3
12m (40 ft)
–
–
100m (328 ft) RF3-0006-4
–
B
5
12m (40 ft)
–
–
100m (328 ft) RF3-0010-4
–
C
7.5
12m (40 ft)
–
1321-M048 150m (492 ft) RF3-0018-4
–
C
10
12m (40 ft)
–
1321-M048 150m (492 ft) RF3-0018-4
–
D
15
12m (40 ft)
–
–
150m (492 ft) RF3-0025-4
–
D
20
12m (40 ft)
–
–
150m (492 ft) 22-RFD036
–
D
25
12m (40 ft)
–
–
150m (492 ft) 22-RFD050
–
D
30
12m (40 ft)
–
–
150m (492 ft) 22-RFD050
–
E
40
30m (98 ft)
22-RFD070
–
–
–
–
E
50
30m (98 ft)
22-RFD070
–
–
–
–
2
25
150m (492 ft) 22-RFD036
–
–
–
–
3
30
150m (492 ft) 22-RFD050
–
–
–
–
3
40
150m (492 ft) 22-RFD070
–
–
–
–
3
50
150m (492 ft) 22-RFD070
–
–
–
–
4
60
150m (492 ft) 22-RFD100
–
–
–
–
5
75
150m (492 ft) 22-RFD100
–
–
–
–
5
100
150m (492 ft) 22-RFD150
–
–
–
–
6
125
150m (492 ft) 22-RFD180
–
–
–
–
6
150
150m (492 ft) 22-RFD180
–
–
–
–
Summary of Contents for 9VT201-007HTNNN
Page 1: ...VTAC 9 AC Drive Firmware Version 3 xx User Manual ...
Page 4: ...soc 2 ...
Page 14: ...P 8 Overview Publication 9VT UM001D EN P Notes ...
Page 56: ...1 42 Installation Wiring Publication 9VT UM001D EN P Notes ...
Page 62: ...2 6 Start Up Publication 9VT UM001D EN P Notes ...
Page 130: ...3 68 Programming and Parameters Publication 9VT UM001D EN P Notes ...
Page 150: ...4 20 Troubleshooting Publication 9VT UM001D EN P Notes ...
Page 176: ...A 26 Supplemental Drive Information Publication 9VT UM001D EN P Notes ...
Page 196: ...B 20 Using the LCD OIM Publication 9VT UM001D EN P Notes ...
Page 212: ...C 16 Application Notes Publication 9VT UM001D EN P Notes ...
Page 223: ......