055 [Maximum Freq]
Sets the highest frequency the drive will
output. Note that this is not maximum
speed which is set in 083 [Overspeed
Limit].
Refer to
Default:
Min/Max:
Units:
130.0 Hz
5.0/400.0 Hz
0.1 Hz
056 [Compensation]
Enables/disables correction options.
Option Descriptions
Reflect Wave
Enables/disables reflected wave overvoltage protection for long
cable lengths. Enable this option for cable lengths longer than
300 feet.
Enable Jerk
Enables/disables the jerk limit in the current limiter that helps to
eliminate overcurrent trips on fast accelerations. In non-FVC
Vector modes, disabling jerk removes a short S-curve at the
start of the accel/decel ramp. Disable if application requires
acceleration time less than 25 seconds.
Ixo AutoCalc
Frame 2, 3, 4, 5, & 6 drives only. Calculates voltage drop due to
leakage inductance. See 064 [Ixo Voltage Drop].
057 [Flux Up Mode]
Amount of DC current equal to current
limit to establish full motor stator flux
before acceleration.
“Manual” (0) = Flux is established for [Flux
Up Time] before acceleration.
“Automatic” (1) = Flux is established for a
calculated time period based on motor
nameplate data. [Flux Up Time] is not
used.
Default:
Options:
0
0
1
“Manual”
“Manual”
“Automatic”
058 [Flux Up Time]
Sets the amount of time the drive will use
to try and achieve full motor stator flux.
When a Start command is issued, DC
current at current limit level is used to
build stator flux before accelerating.
Default:
Min/Max:
Units:
0.00 Secs
0.00/5.00 Secs
0.01 Secs
059 [SV Boost Filter]
Sets the amount of filtering used to boost
voltage during Sensorless Vector
operation.
Default:
Min/Max:
Units:
500
0/32767
1
F
ile
Gr
oup
No
.
Parameter Name and Description
See
page 3-2
for symbol descriptions
Values
Re
lated
1
0
x
1
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1
=Enabled
0
=Disabled
x =
R
eserved
Bit #
Factory Default Bit Values
R
eflect
W
av
e
Enab
le Jer
k
Ixo
A
utoCalc
N
ibble 1
N
ibble 2
N
ibble 3
N
ibble 4
2…6
Summary of Contents for 9VT201-007HTNNN
Page 1: ...VTAC 9 AC Drive Firmware Version 3 xx User Manual ...
Page 4: ...soc 2 ...
Page 14: ...P 8 Overview Publication 9VT UM001D EN P Notes ...
Page 56: ...1 42 Installation Wiring Publication 9VT UM001D EN P Notes ...
Page 62: ...2 6 Start Up Publication 9VT UM001D EN P Notes ...
Page 130: ...3 68 Programming and Parameters Publication 9VT UM001D EN P Notes ...
Page 150: ...4 20 Troubleshooting Publication 9VT UM001D EN P Notes ...
Page 176: ...A 26 Supplemental Drive Information Publication 9VT UM001D EN P Notes ...
Page 196: ...B 20 Using the LCD OIM Publication 9VT UM001D EN P Notes ...
Page 212: ...C 16 Application Notes Publication 9VT UM001D EN P Notes ...
Page 223: ......