Application Notes
C-11
This function stops (sleep) and starts (wake) the drive based on
separately configurable analog input levels rather than discrete start and
stop signals. When enabled in “Direct” mode, the drive will start (wake)
when an analog signal is greater than or equal to the user specified
[Wake Level], and stop the drive when an analog signal is less than or
equal to the user specified [Sleep Level].
Definitions
•
Wake - A start command generated when the analog input value
remains above [Wake Level] for a time greater than [Wake Time].
•
Sleep - A Stop command generated when the analog input value
remains below [Sleep Level] for a time greater than [Sleep Time].
•
Speed Reference – The active speed command to the drive as
selected by drive logic and [Speed Ref x Sel].
•
Start Command - A command generated by pressing the Start button
on the OIM, closing a digital input programmed for Start, Run, Run
Forward or Run Reverse. The source is set by [Logic Source Sel].
Refer to
Sleep Wake Mode
Summary of Contents for 9VT201-007HTNNN
Page 1: ...VTAC 9 AC Drive Firmware Version 3 xx User Manual ...
Page 4: ...soc 2 ...
Page 14: ...P 8 Overview Publication 9VT UM001D EN P Notes ...
Page 56: ...1 42 Installation Wiring Publication 9VT UM001D EN P Notes ...
Page 62: ...2 6 Start Up Publication 9VT UM001D EN P Notes ...
Page 130: ...3 68 Programming and Parameters Publication 9VT UM001D EN P Notes ...
Page 150: ...4 20 Troubleshooting Publication 9VT UM001D EN P Notes ...
Page 176: ...A 26 Supplemental Drive Information Publication 9VT UM001D EN P Notes ...
Page 196: ...B 20 Using the LCD OIM Publication 9VT UM001D EN P Notes ...
Page 212: ...C 16 Application Notes Publication 9VT UM001D EN P Notes ...
Page 223: ......