Troubleshooting
4-11
IR Volts
Range
25
➁
The drive auto tuning default is “Calculate” and the value calculated for IR
Drop Volts is not in the range of acceptable values. This alarm should clear
when all motor nameplate data is properly entered.
Ixo Vlt Rang
28
➁
Motor leakage inductance is out of range.
MaxFreq
Conflict
23
➁
The sum of [Maximum Speed] and [Overspeed Limit] exceeds [Maximum
Freq]. Raise [Maximum Freq] or lower [Maximum Speed]
and/or [Overspeed Limit] so that the sum is less than or equal to
[Maximum Freq].
Motor Type
Cflct
21
➁
Parameter 040 [Motor Type] has been set to 1 “Synchr Reluc” or 2 “Synchr
PM” and one or more DC functions (for example DC Boost, DC Brake, etc.)
have been activated. DC injection functions are incompatible with
synchronous motors and may demagnetize them.
NP Hz
Conflict
22
➁
Fan/pump mode is selected in [Torq Perf Mode] and the ratio of [Motor NP
Hertz] to [Maximum Freq] is greater than 26.
Power Loss
3
➀
Drive has sensed a power line loss.
Prechrg Actv
1
➀
Drive is in the initial DC bus precharge state.
Sleep Config
29
➁
Sleep/Wake configuration error. With [Sleep-Wake Mode] = “Direct,” possible
causes include: drive is stopped and [Wake Level] < [Sleep Level].“Stop=CF,”
“Run,” “Run Forward,” or “Run Reverse.” is not configured in [Digital Inx Sel].
Speed Ref
Cflct
27
➁
[Speed Ref x Sel] or [PI Reference Sel] is set to “Reserved”.
UnderVoltage 2
➀
The bus voltage has dropped below a predetermined value.
VHz Neg
Slope
24
➁
[Torq Perf Mode] = “Custom V/Hz” and the V/Hz slope is negative.
Waking
11
➀
The Wake timer is counting toward a value that will start the drive.
(1)
See
for a description of alarm types.
Alarm
No.
Ty
p
e
(1
)
Description
Summary of Contents for 9VT201-007HTNNN
Page 1: ...VTAC 9 AC Drive Firmware Version 3 xx User Manual ...
Page 4: ...soc 2 ...
Page 14: ...P 8 Overview Publication 9VT UM001D EN P Notes ...
Page 56: ...1 42 Installation Wiring Publication 9VT UM001D EN P Notes ...
Page 62: ...2 6 Start Up Publication 9VT UM001D EN P Notes ...
Page 130: ...3 68 Programming and Parameters Publication 9VT UM001D EN P Notes ...
Page 150: ...4 20 Troubleshooting Publication 9VT UM001D EN P Notes ...
Page 176: ...A 26 Supplemental Drive Information Publication 9VT UM001D EN P Notes ...
Page 196: ...B 20 Using the LCD OIM Publication 9VT UM001D EN P Notes ...
Page 212: ...C 16 Application Notes Publication 9VT UM001D EN P Notes ...
Page 223: ......