3-42
Programming and Parameters
UT
ILITY
MOP Config
194 [Save MOP Ref]
Enables/disables the feature that saves the present MOP frequency reference at
power down or at stop.
195 [MOP Rate]
Sets rate of change of the MOP reference
in response to a digital input.
Default:
Min/Max:
Units:
1.0 Hz/s
0.2/400.0 Hz/s
0.1 Hz/s
Dri
ve Memory
196 [Param Access Lvl]
Selects the parameter display level.
Basic = Reduced param. set
Advanced = Full param. set
Default:
Options:
1
2
Read Only
“Standard”
“Advanced”
197 [Reset To Defalts]
Resets all parameter values (except
parameters 196, 201 & 202) to defaults.
Option 1 resets drive to factory settings.
Options 2 and 3 will reset drive to
alternate voltage and current rating.
Low Voltage = 400V class defaults
High Voltage = 480V class defaults
Important: Internal fan voltage on frame
5 drives may need to be changed when
using option 2 or 3.
Default:
Options:
0
0
1
2
3
“Ready”
“Ready”
“Factory”
“Low Voltage”
“High Voltage”
198 [Load Frm Usr Set]
Loads a previously saved set of
parameter values from a selected user set
location in drive non-volatile memory to
active drive memory. An F-Key on the
LCD OIM can be configured for this
function. Refer to
.
Default:
Options:
0
0
1
2
3
“Ready”
“Ready”
“User Set 1”
“User Set 2”
“User Set 3”
199 [Save To User Set]
Saves the parameter values in active drive
memory to a user set in drive nonvolatile
memory. An F-Key on the LCD OIM can
be configured for this function. Refer to
Default:
Options:
0
0
1
2
3
“Ready”
“Ready”
“User Set 1”
“User Set 2”
“User Set 3”
200 [Reset Meters]
Resets selected meters to zero.
Default:
Options:
0
0
1
2
“Ready”
“Ready”
“MWh”
“Elapsed Time”
F
ile
Gr
oup
No
.
Parameter Name and Description
See
page 3-2
for symbol descriptions
Values
Re
lated
0
x
x
1
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1
=
S
ave
0
=Do
N
ot
S
ave
x =
R
eserved
Bit #
Factory Default Bit Values
A
t P
owr Do
wn
A
t
S
top
N
ibble 1
N
ibble 2
N
ibble 3
N
ibble 4
Summary of Contents for 9VT201-007HTNNN
Page 1: ...VTAC 9 AC Drive Firmware Version 3 xx User Manual ...
Page 4: ...soc 2 ...
Page 14: ...P 8 Overview Publication 9VT UM001D EN P Notes ...
Page 56: ...1 42 Installation Wiring Publication 9VT UM001D EN P Notes ...
Page 62: ...2 6 Start Up Publication 9VT UM001D EN P Notes ...
Page 130: ...3 68 Programming and Parameters Publication 9VT UM001D EN P Notes ...
Page 150: ...4 20 Troubleshooting Publication 9VT UM001D EN P Notes ...
Page 176: ...A 26 Supplemental Drive Information Publication 9VT UM001D EN P Notes ...
Page 196: ...B 20 Using the LCD OIM Publication 9VT UM001D EN P Notes ...
Page 212: ...C 16 Application Notes Publication 9VT UM001D EN P Notes ...
Page 223: ......