Troubleshooting
4-9
Alarm Queue
Important: This information applies only to drive Frames 2, 3, 4, 5, &
6.
The drive automatically retains a history of alarms that have occurred in
the alarm queue. The alarm queue is accessed using the OIM or PC
software.
The alarm queue holds the eight most recent alarms. The last alarm to
occur is indicated in queue entry #1. As new alarms are logged into the
queue, existing alarm entries are shifted (for example, entry #1 will
move to entry #2). Once the queue is full, older alarms are discarded
from the queue as new alarms occur.
All entries in the alarm queue are retained if power is lost. Alarms are
automatically cleared when the alarm condition goes away.
The alarm queue can be cleared using the OIM by selecting “Clr Alarm
Queue”, or by using a PC software tool.
Alarms are automatically cleared when the condition that caused the
alarm is no longer present.
Clearing Alarms