Appendix
A
Supplemental Drive Information
For information on…
See page…
Drive, Fuse & Circuit Breaker Ratings
Specifications
Category
Specification
Protection
Drive
208V 480V
AC Input Overvoltage Trip:
247VAC
570VAC
AC Input Undervoltage Trip:
120VAC
280VAC
Bus Overvoltage Trip:
405VDC
810VDC
Bus Undervoltage Output Shutoff:
300VDC
407V DC
Bus Undervoltage Fault Level:
160VDC
300VDC
Nominal Bus Voltage:
281VDC
648VDC
All Drives
Heat Sink Thermistor:
Monitored by microprocessor overtemp trip
Drive Overcurrent Trip
Software Current Limit:
Hardware Current Limit:
Instantaneous Current Limit:
20-160% of rated current
200% of rated current (typical)
220-300% of rated current (dependent on drive rating)
Line transients:
up to 6000 volts peak per IEEE C62.41-1991
Control Logic Noise Immunity:
Showering arc transients up to 1500V peak
Power Ride-Thru:
15 milliseconds at full load
Logic Control Ride-Thru:
0.5 seconds minimum, 2 seconds typical
Ground Fault Trip:
Phase-to-ground on drive output
Short Circuit Trip:
Phase-to-phase on drive output
Environmen
t
Altitude:
1000 m (3300 ft) max. without derating
Maximum Surrounding Air
Temperature without derating
IP30, NEMA Type 1:
0 to 50 degrees C (32 to 122 degrees F), typical. See pages
for exceptions.
Storage Temperature (all const.):
–40 to 70 degrees C (–40 to 158 degrees F)
Atmosphere
Important: Drive must not be installed in an area where the
ambient atmosphere contains volatile or corrosive gas,
vapors or dust. If the drive is not going to be installed for a
period of time, it must be stored in an area where it will not
be exposed to a corrosive atmosphere.
Relative Humidity:
5 to 95% non-condensing
Shock:
15G peak for 11ms duration (
±
1.0 ms)
Vibration:
0.152 mm (0.006 in.) displacement, 1G peak
Summary of Contents for 9VT201-007HTNNN
Page 1: ...VTAC 9 AC Drive Firmware Version 3 xx User Manual ...
Page 4: ...soc 2 ...
Page 14: ...P 8 Overview Publication 9VT UM001D EN P Notes ...
Page 56: ...1 42 Installation Wiring Publication 9VT UM001D EN P Notes ...
Page 62: ...2 6 Start Up Publication 9VT UM001D EN P Notes ...
Page 130: ...3 68 Programming and Parameters Publication 9VT UM001D EN P Notes ...
Page 150: ...4 20 Troubleshooting Publication 9VT UM001D EN P Notes ...
Page 176: ...A 26 Supplemental Drive Information Publication 9VT UM001D EN P Notes ...
Page 196: ...B 20 Using the LCD OIM Publication 9VT UM001D EN P Notes ...
Page 212: ...C 16 Application Notes Publication 9VT UM001D EN P Notes ...
Page 223: ......