1-32
Installation/Wiring
Table 1.L I/O Terminal Designations (Frames 2…6)
Important:
Frame 2…6 drives can be identified by a vertically oriented I/O
Terminal Block which has 32 terminals. See
.
No. Signal
Fa
ct
o
ry
De
fau
lt
Description
Re
lated
Pa
ra
m
.
1
Anlg Volts In 1 (–)
(2)
Isolated
(3)
, bipolar, differential,
±
10V, 11 bit & sign, 88k ohm input
impedance.
320 -
327
2
Anlg Volts In 1 (+)
3
Anlg Volts In 2 (–)
Isolated
(4)
, bipolar, differential,
±
10V, 11 bit & sign, 88k ohm input
impedance.
4
Anlg Volts In 2 (+)
5
Pot Common
–
For (+) and (–) 10V pot references.
6
Anlg Volts Out 1 (–)
Bipolar,
±
10V, 11 bit & sign, 2k ohm
minimum load.
340 -
344
7
Anlg Volts Out 1 (+)
8
Anlg Current Out 1 (–)
4-20mA, 11 bit & sign, 400 ohm
maximum load.
9
Anlg Current Out 1 (+)
10
Reserved for Future Use
11
Digital Out 1 – N.C.
(1)
Fault
Max. Resistive Load:
240V AC/30V DC – 1200VA, 150W
Max. Current: 5A, Min. Load: 10mA
Max. Inductive Load:
240V AC/30V DC – 840VA, 105W
Max. Current: 3.5A, Min. Load: 10mA
380 -
387
12
Digital Out 1 Common
13
Digital Out 1 – N.O.
NOT Fault
14
Digital Out 2 – N.C.
NOT Run
15
Digital Out 2 Common
16
Digital Out 2 – N.O.
Run
17
Anlg Current In 1 (–)
Isolated
, 4-20mA, 11 bit & sign,
124 ohm input impedance.
320 -
327
18
Anlg Current In 1 (+)
19
Anlg Current In 2 (–)
Isolated
, 4-20mA, 11 bit & sign,
124 ohm input impedance.
20
Anlg Current In 2 (+)
21
–10V Pot Reference
–
2k ohm minimum.
22
+10V Pot Reference
–
23
Reserved for Future Use
24
+24VDC
–
Drive supplied logic input power.
(5)
25
Digital In Common
–
26
24V Common
–
Common for internal power supply.
27
Digital In 1
Run
Opto isolated
Low State: less than 5V AC/DC
High State: greater than 20V AC/DC
11.2 mA DC
361 -
366
28
Digital In 2
Clear Faults
29
Digital In 3
Function Loss
30
Digital In 4
Enable
31
Digital In 5
OIM Control
32
Digital In 6
Purge
(1)
Contacts in unpowered state. Any relay programmed as Fault or Alarm will energize (pick up) when
power is applied to drive and deenergize (drop out) when a fault or alarm exists. Relays selected
for other functions will energize only when that condition exists and will deenergize when condition
is removed.
(2)
These inputs/outputs are dependant on a number of parameters. See “Related Parameters.”
(3)
Differential Isolation - External source must be maintained at less than 160V with respect to PE.
Input provides high common mode immunity.
(4)
Differential Isolation - External source must be less than 10V with respect to PE.
(5)
150mA maximum Load.
1
16
32
Summary of Contents for 9VT201-007HTNNN
Page 1: ...VTAC 9 AC Drive Firmware Version 3 xx User Manual ...
Page 4: ...soc 2 ...
Page 14: ...P 8 Overview Publication 9VT UM001D EN P Notes ...
Page 56: ...1 42 Installation Wiring Publication 9VT UM001D EN P Notes ...
Page 62: ...2 6 Start Up Publication 9VT UM001D EN P Notes ...
Page 130: ...3 68 Programming and Parameters Publication 9VT UM001D EN P Notes ...
Page 150: ...4 20 Troubleshooting Publication 9VT UM001D EN P Notes ...
Page 176: ...A 26 Supplemental Drive Information Publication 9VT UM001D EN P Notes ...
Page 196: ...B 20 Using the LCD OIM Publication 9VT UM001D EN P Notes ...
Page 212: ...C 16 Application Notes Publication 9VT UM001D EN P Notes ...
Page 223: ......