Appendix B Quickstarts
MyAppData.HscMode
allows the user to specify the type of operation in which the HSC will use
to count. See
HSC Mode (HSCAPP.HSCMode) on page 204
for more information about HSC
modes. See
for the list available modes.
Modes 1, 3, 5, 7, and 9 will only work when an ID of 0, 2, or 4 is set due to the fact that these
modes use reset and hold. Modes 0, 2, 4, 6, and 8 will work on any ID. Modes 6…9 will only work
when an encoder is connected to the controller. Use the HSC ID chart as a reference to wire
the encoder to the controller.
MyAppData.HPSetting
,
MyAppData.LPSetting
,
MyAppData.OFSetting
, and
MyAppData.UFSetting
are all user-defined variables that represent the counting range of the
gives an example of a range of values that can be set for these
variables.
Figure 29 - Range of Values
MyAppData.OutputMask
along with
MyAppData.HPOutput
and
MyAppData.LPOutput
allows
the user to specify which embedded outputs can be turned on when a High Preset or Low
Preset is reached. These variables use a combination of decimals and binary numbers to
specify the embedded outputs that are able to turn on/off.
Thus, in our example, we first set the Output Mask to a decimal value of 3 which, when
converted to binary, is equal to 0011. This means that now outputs O0 and O1 can be turned
On/Off.
We have set the HPOutput to a decimal value of 1, which, when converted to binary, is equal to
0001. This means that when a High Preset is reached, output O0 will turn on and stay on until
the HSC is reset or the counter counts back down to a Low Preset. The LPOutput works same
way as the HPOutput except an output will be turned on when a Low Preset is reached.
Table 70 - HSC Operating Modes
Mode
Number
Type
0
Up Counter – The accumulator is immediately cleared (0) when it reaches the high preset. A low
preset cannot be defined in this mode.
1
Up Counter with external reset and hold – The accumulator is immediately cleared (0) when it
reaches the high preset. A low preset cannot be defined in this mode.
2
Counter with external direction
3
Counter with external direction, reset, and hold
4
Two input counter (up and down)
5
Two input counter (up and down) with external reset and hold
6
Quadrature counter (phased inputs A and B)
7
Quadrature counter (phased inputs A and B) with external reset and hold
8
Quadrature X4 counter (phased inputs A and B)
9
Quadrature X4 counter (phased inputs A and B) with external reset and hold
+2,147,483,647 maximum
-2,147,483,648
Overflow
High Preset
0
Low Preset
Underflow
HscAppData.OFSetting
HscAppData.HPSetting
HscAppData.LPSetting
HscAppData.UFSetting
Variable