142
Rockwell Automation Publication 2080-UM002N-EN-E - November 2022
Chapter 8 EtherNet/IP Network
LogicCommand.14
BIT
Hold the existing frequency when sync time is set to
enable speed synchronization.
1 = Sync enable
SyncEnabled
LogicCommand.15
BIT
Disable the traverse function
1 = Traverse disable
TravDisable
FreqCommand
INT
Control the reference speed of the drive.
In units of 0.01 Hz
Table 20 - PowerFlex 520-series Drive Output Assembly Data (Position Mode) (Continued)
Name
Data Type Description
Value
Comment
Table 21 - PowerFlex 520-series Drive Input Assembly Data (Velocity Mode)
Name
Data Type Description
Value
Comment
DriveStatus
INT
DriveStatus.0
BIT
Indicates whether the drive is ready for operation.
0 = Not ready
1 = Ready
Ready
DriveStatus.1
BIT
Indicates whether the drive is operating.
0 = Not active
1 = Active (Running)
Active
DriveStatus.2
BIT
Indicates the command direction.
0 = Cmd reverse
1 = Cmd forward
CommandDir
DriveStatus.3
BIT
Indicates the rotating direction.
0 = Rotating reverse
1 = Rotating forward
ActualDir
DriveStatus.4
BIT
Indicates the acceleration state.
0 = Not accelerating
1 = Accelerating
Accelerating
DriveStatus.5
BIT
Indicates the deceleration state.
0 = Not decelerating
1 = Decelerating
Decelerating
DriveStatus.6
BIT
Reserved.
DriveStatus.7
BIT
Indicates the fault state.
0 = Not faulted
1 = Faulted
Faulted
DriveStatus.8
BIT
Indicates that the drive is at reference speed.
0 = Not at reference
1 = At reference
AtReference
DriveStatus.9
BIT
Indicates that the main frequency is controlled by the
active communication.
1 = Main frequency controlled by active
comm
CommFreqCnt
DriveStatus.10
BIT
Indicates that the operation command is controlled by
the active communication.
1 = Operation command controlled by
active comm
CommLogicCnt
DriveStatus.11
BIT
Indicates that the parameters are locked.
1 = Parameters are locked
ParmsLocked
DriveStatus.12
BIT
Indicates the Digital Input 1 status.
DigIn1Active
DriveStatus.13
BIT
Indicates the Digital Input 2 status.
DigIn2Active
DriveStatus.14
BIT
Indicates the Digital Input 3 status.
DigIn3Active
DriveStatus.15
BIT
Indicates the Digital Input 4 status.
DigIn4Active
OutputFreq
INT
Display the reference speed of the drive.
In units of 0.01 Hz.
Table 22 - PowerFlex 520-series Drive Output Assembly Data (Velocity Mode)
Name
Data Type Description
Value
Comment
LogicCommand
INT
LogicCommand.0
BIT
Perform a normal stop.
0 = Not normal stop
1 = Normal stop
Stop
LogicCommand.1
BIT
Command the drive the start.
0 = Not start
1 = Start
Start
LogicCommand.2
BIT
Command the drive to jog.
0 = Not jog
1 = Jog
Jog
LogicCommand.3
BIT
Clear drive fault.
0 = Not clear fault
1 = Clear fault
ClearFaults
LogicCommand.4
BIT
Command the direction of the drive.
00 = No command
01 = Forward command
10 = Reverse command
11 = No command
Forward
LogicCommand.5
BIT
Reverse
LogicCommand.6
BIT
Force keypad control.
0 = Not keypad control
1 = Forced keypad control
ForceKeypadCtrl
LogicCommand.7
BIT
Increases the value of drive parameter A427 [MOP Freq]
at the rate set in A430 [MOP Time].
0 = Not increment
1 = MOP increment
MOPIncrement