DN-Series Integrated Programmable Controls
DOAS
38
6.2 DEHUMIDIFICATION
The dehumidification is performed with the cooling. Therefore, the unit must have cooling
enabled. It may also have HGRH enabled here, used for reheat during dehumidification.
The setting for changeover is in
Control Settings
. Dehumidification mode will be on at the
dehumidification se the hysteresis value set here. It will go out of dehumidification
mode below the setpoint.
This screen will not show up if dehumidification is disabled in the prior screen.
TEMPERING CONTROL
Increasing dew point turns
mode ON at se hysteresis
Decreasing dew point
turns mode OFF at setpoint
Hysteresis
Se Hysteresis
Setpoint
OFF
ON
DEW POINT
The status can be monitored in
Unit Status.