DN-Series Integrated Programmable Controls
DOAS
112
SYSTEM MONITORING
TYPE
INSTANCE
VARIABLE NAME
DESCRIPTION
VALUE
RANGE
READ/WRITE
(RET)
Binary Input
514
Al_SA_StaticPress.
Active
SA Static Pressure Level
Alarm
OK/Alarm Read_NoWrite
Binary Input
515
Al_CO2.Active
CO2 Level Alarm
OK/Alarm Read_NoWrite
Binary Input
516
Al_SupAir_Low_Temp_
Warn.Active
Supply Air Low
Temperature Warning
OK/Alarm Read_NoWrite
Binary Input
517
Al_SupAir_Low_Temp_
Alarm.Active
Supply Air Low
Temperature Alarm
OK/Alarm Read_NoWrite
Binary Input
518
Al_SupAir_Hi_Temp_
Warn.Active
Supply Air High
Temperature Warning
OK/Alarm Read_NoWrite
Binary Input
519
Al_SupAir_Hi_Temp_
Alarm.Active
Supply Air High
Temperature Alarm
OK/Alarm Read_NoWrite
Binary Input
521
Al_EA_StaticPress.
Active
EA Static Pressure Level
Alarm
OK/Alarm Read_NoWrite
Binary Input
530
Al_OA_Temp_Prb.
Active
OA Temperature Sensor
Open or Short
OK/Alarm Read_NoWrite
Binary Input
531
Al_OA_Hum_Prb.Active OA Relative Humidity
Transmitter Out of Range
OK/Alarm Read_NoWrite
Binary Input
532
Al_RA_Temp_Prb.
Active
RA Temperature Sensor
Open or Short
OK/Alarm Read_NoWrite
Binary Input
533
Al_RA_Hum_Prb.Active RA Relative Humidity
Transmitter Out of Range
OK/Alarm Read_NoWrite
Binary Input
534
Al_SA_Temp_Prb.
Active
SA Temperature Sensor
Open or Short
OK/Alarm Read_NoWrite
Binary Input
535
Al_EA_Temp_Prb.
Active
EA Temperature Sensor
Open or Short
OK/Alarm Read_NoWrite
Binary Input
536
Al_OA_Flt_Press_Prb.
Active
OA Filter Pressure
Transmitter Out of Range
OK/Alarm Read_NoWrite
Binary Input
537
Al_RA_Flt_Press_Prb.
Active
RA Filter Pressure
Transmitter Out of Range
OK/Alarm Read_NoWrite
Binary Input
538
Al_OA_Flow_Rate_Prb.
Active
OA Flow Rate Pressure
Transmitter Out of Range
OK/Alarm Read_NoWrite
Binary Input
539
Al_EA_Flow_Rate_Prb.
Active
EA Flow Rate Pressure
Transmitter Out of Range
OK/Alarm Read_NoWrite
Binary Input
540
Al_CO2_Level_Prb.
Active
CO2 Level Transmitter
Out of Range
OK/Alarm Read_NoWrite
Binary Input
541
Al_Duct_Press_Prb.
Active
Duct Pressure
Transmitter Out of Range
OK/Alarm Read_NoWrite
Binary Input
542
Al_Supply_Temp_Prb.
Active
Conditioned Air (CA)
Temperature Sensor
Open or Short
OK/Alarm Read_NoWrite
Binary Input
543
Al_Coil_LAT_Prb.Active Coil LAT Sensor Open or
Short
OK/Alarm Read_NoWrite
Binary Input
560
Al_OA_Flt_Press.
Active
OA Filter Needs Change
OK/Alarm Read_NoWrite
Binary Input
561
Al_RA_Flt_Press.
Active
RA Filter Needs Change
OK/Alarm Read_NoWrite
Binary Input
562
Al_UnitLife_DOAS.
Active
Unit Service Request
OK/Alarm Read_NoWrite
Binary Input
564
Al_SupplyFanLife.
Active
Supply Fan Service
Request
OK/Alarm Read_NoWrite