111
1.800.627.4499
DN-Series Integrated Programmable Controls
DOAS
SYSTEM MONITORING
TYPE
INSTANCE
VARIABLE NAME
DESCRIPTION
VALUE
RANGE
READ/WRITE
(RET)
Binary Input
21
DOAS_UnitOn
DOAS Unit On Status
Off/On
Read_NoWrite
Binary Input
22
OfflineAlrm_CPCOE_1.
Active
Offline Alarm expansion
module
OK/Alarm Read_NoWrite
Binary Input
23
OfflineDOAStoREF.
Active
Offline DOAS to
Refrigeration Controller
OK/Alarm Read_NoWrite
Binary Input
24
Al_SupplyFan.Active
Supply Fan Start Alarm
OK/Alarm Read_NoWrite
Binary Input
25
Al_ExhaustFan.Active
Exhaust Fan Start Alarm
OK/Alarm Read_NoWrite
Binary Input
49
Recirc_Damp.Val
Recirculation Damper
Command
Close/
Open
Read_NoWrite
Binary Input
57
Heating_Enable_2.Val
Heating Stage 2
Off/On
Read_NoWrite
Binary Input
60
Econ_Active
Economizer Active?
No/Yes
Read_NoWrite
Binary Input
61
DehumidMode_On
Dehumidification Mode
On?
No/Yes
Read_NoWrite
Binary Input
67
Unocc_Mode
Unoccupied Mode Status
Occ/
Unocc
Read_NoWrite
Binary Input
68
Unocc_HTG
Unoccupied Heating
Status
Off/On
Read_NoWrite
Binary Input
69
Unocc_CLG
Unoccupied Cooling
Status
Off/On
Read_NoWrite
Binary Input
70
DefrostOn
Frost control On Status
Off/On
Read_NoWrite
Binary Input
72
Any_Alarm_Out.Val
Any Alarm is True Status
OK/Alarm Read_NoWrite
Binary Input
499
SeriousAlarm_RefUnit
Alarm in Refrigeration
Unit
OK/Alarm Read_NoWrite
Binary Input
500
Al_retain.Active
Too Many Writes to
Retained Memory
OK/Alarm Read_NoWrite
Binary Input
501
Al_Err_retain_write.
Active
Too Many Writes to
Retained Memory
OK/Alarm Read_NoWrite
Binary Input
502
Al_Device_Test.Active
Unit Was Left In Device
Test Mode
OK/Alarm Read_NoWrite
Binary Input
503
Al_BMS_Offline.Active
BMS Is Offline
OK/Alarm Read_NoWrite
Binary Input
504
OfflineAlrm_CPCOE_1.
Active
Offline Alarm Expansion
Module
OK/Alarm Read_NoWrite
Binary Input
505
CfgErrAlrm_CPCOE_1.
Active
Expansion Module Config
Error
OK/Alarm Read_NoWrite
Binary Input
506
OfflineDOAStoREF.
Active
Offline DOAS to
Refrigeration Controller
OK/Alarm Read_NoWrite
Binary Input
507
OfflineReftoInv.Active
Offline Refrigeration
Controller to Inverter
OK/Alarm Read_NoWrite
Binary Input
510
Al_SupplyFan.Active
Supply Fan Start Alarm
OK/Alarm Read_NoWrite
Binary Input
511
Al_ExhaustFan.Active
Exhaust Fan Start Alarm
OK/Alarm Read_NoWrite
Binary Input
512
Al_SA_Airflow.Active
Supply Airflow Out of
Tolerance Alarm
OK/Alarm Read_NoWrite
Binary Input
513
Al_EA_Airflow.Active
Exhaust Airflow Out of
Tolerance Alarm
OK/Alarm Read_NoWrite