DN-Series Integrated Programmable Controls
DOAS
CONTROLLER UPDATES
The variables that are logged are as listed here.
VARIABLE
VARIABLE
VARIABLE
OA_Temp.Val
Cooling_LAT.Val
SuctPress_1.Val
OA_Hum.Val
HGRH_Command.Val
OA_Dewpoint
RA_Hum.Val
Any_Alarm_Out.Val
RA_Dewpoint
SA_Temp.Val
DscgTemp_2.Val
RegCool
EA_Temp.Val
DscgPress_2.Val
GEN_RefrigerationStage
Cooling_Command.Val
DscgPress_1.Val
GEN_CompSpeedFeedback_PCT
Heating_Command.Val
SuctTemp_2.Val
GEN_DemandtoVarSpeedCompressor_1
RA_Temp.Val
SuctPress_2.Val
EVD_VariableSpeed_EEV_PosPercent_Val
OA_Enthalpy
SuctTemp_1.Val
Bypass_Command.Val
DscgTemp_1.Val
You can view the parameter files that were created in
Restore Parameters (Settings)
. You can
also share them between controllers. An excerpt of a file is shown below.
#Ver.1.0 cpCO Family Exported Configuration file
11.3 VIEWING PARAMETER FILES
#VARIABLE
DESCRIPTION
DATA TYPE DEFAULT VALUE
BACnet_Mapping
UINT
0
BMSMng.BACnetPort
UDINT
47808
BMSMng.BMS_Address_RS485
UINT
4
BMSMng.BMS_BACnetDeviceInstance
UDINT
5002
BMSMng.BMS_BACnetMSTP_MaxInfoFrames UINT
20
BMSMng.BMS_BACnetMSTP_MaxMaster
UINT
127
BMSMng.BMS_BACnet_CmdTimeout
UINT
1500
BMSMng.BMS_BACnet_Timout
UINT
3000
BMSMng.BMS_Baud_Msk
UINT
2
BMSMng.BMS_Baud_RS485
UDINT
19200
BMSMng.BMS_Modbus_Timeout
UINT
3000
BMSMng.BMS_Parity_MSK
USINT
0