69
1.800.627.4499
DN-Series Integrated Programmable Controls
DOAS
SPECIAL FEATURES
The system allows you to use a room temperature and humidity sensor in place of the return air
temperature and humidity sensor. One use for this is when you have unoccupied operation when
the fans are off, you will be able to get a temperature indicative of the actual room temperature.
This feature is useful when feeding a single zone. It requires the removal of the return sensors
and replace them with the room sensor. The setting here will change the word “return” to
“room” on the main screen to eliminate confusion.
8.3 USE ROOM TEMP AND HUMIDITY RATHER THAN RETURN
The Room Temperature and Humidity Sensor is P/N 102397 Wall Mount, RTH-W.
CHANGES
NAME
REV.
DATE
SCHEME
Field Wiring
RenewAire
1
A
B
C
D
E
Updated Sensor Nomenclature
2
5/5/2020
austine
3
5/5/2020
austine
Updated External Temp and Humidity Sensor from OA to RA
4
5/5/2020
austine
Added Any Alarm Output
5
5/8/2020
austine
Updated Ground Locations
6
4/4/2022
shreyat
Updated controller gnd connections
3
DN-2,3-Jxxxxx33,34,35--xGxExx--xx_006
2
3
4
5
6
7
8
9
10
11
12
13
X3
22
X3
23
X3
24
X3
25
X3
26
X3
27
X3
28
X3
29
X3
30
X3
21
X4
31
X4
32
X4
33
X4
34
X4
35
Sensor 24 VAC
EXP GND
EXP U3
EXP U4
EXP U5
EXP U6
EXP U7
EXP U8
EXP U9
EXP U10
EXP GND
EXP NO 3
EXP NO 4
EXP NO 5
0 - 10 VDC Input, CO2 Level/VOC
0 - 10 VDC Output, Bypass Damper
0 - 10 VDC Input, Cooling Coil LAT
0 - 10 VDC Input, Duct Pressure
Unit Supply Temp
10K Carel NTC
0 - 10 VDC Output, Cooling Modulation
0 - 10 VDC Output, Heating Modulation
Open = Heating, Closed = Cooling
Cooling Stage 1
Cooling Stage 2
RED
RED
BLK
BLK
NO 4
Accy COM
Accy COM
Accy 24 VAC
X1
4
X1
3
X1
2
X1
1
COM
HOT
DAMPER2
EA/RA
COM
HOT
DAMPER1
OA/FA
RED
BLK
EFEN2
OF1
Factory Jumper
Factory Jumper
SD2
NO 3
Accy COM
X1
7
X1
8
X1
6
EF ECM Enable
NO 1
NO 2
X1
10
X2
12
X2
11
X1
9
EXP C1/2
EXP NO 2
EXP NO 1
Unit Enable
GND
SF ECM Enable
24 VDC
EF Only Enable
Sensor 24 VAC
C1/2
X2
20
X2
19
X2
18
X2
17
X2
16
X2
15
X2
14
X2
13
COM
HOT
DAMPER3
Recirc
Exh Fan Only Enable
Overflow Switch
Smoke Detector
NO 5
X1
5
EXP C3/4/5
Vin
Vout
GND
Duct
Pressure Sensor
0 - 10 VDC Output, HGRH Modulation
COM
HOT
Vin
D4
Face/Bypass
RED
BLK
GRY
T13 ( - )
T12 (+)
Gas Module
For 10:1
Heating Enable/Stage 1
Heating Stage 2
T2
T1
Gas Module
T10(-) For 5:1
T11(+)
External
X4
40
X4
39
X4
38
X4
37
X4
36
+
-
T
O
T
Temp/Humidity Sensor
RA TEMP
RA HUM
RA Temp\Red
RA Humid\Wht
Accy COM
Sensor 24 VAC
GND
BU
02-3-B
02-4-B
02-9-A
It is possible to set different limits for the heating and cooling occupied and unoccupied
setpoints. The defaults are shown in these screens. This will limit the users in the front non-
password protected screens from setting extreme setpoints.
8.4 LIMIT SETPOINT RANGES FOR USERS
Normally the 1-stage and 2-stage heat pumps use the cooling outputs for the heat pump and
the heating outputs for auxiliary heat. If for some reason the heater is actually a 1-stage or
2-stage heater, you can set this setting to “No” and the unit will use the heating outputs.
8.5 USE HEATING OUTPUTS FOR STAGING