DN-Series Integrated Programmable Controls
DOAS
106
BMS ACCESS
The license status can be viewed in a later screen. Refer to
Adding a BACnet License
for
more information.
Once a protocol has been selected, additional BMS programming screens will appear. Change
settings as needed. After the BMS protocol has been selected and protocol options have been
selected, cycle power to the controller.
RenewAire units Are BTL listed by CAREL. They allow the BMS to write to the present value by
default. This means that if the BMS writes to a setpoint that setpoint can be changed by the
local HMI display. (Last one in wins). Priority array is not supported.
Setpoints, in general, are saved in EEPROM memory and maintained on power loss. These are
referred to as RETAINED. For retained values, DO NOT write to these values constantly. Doing
so will flag an alarm and can damage the controller. If you have a need to write to a value
constantly, contact TSS to discuss options.
Older units wrote to the priority array. This was cumbersome to support. They also had limited
mapping. If upgrading from an older version and you want to keep that mapping, change the
setting below to “Pri Array legacy.” The mapping is quite different and is supported in the older
documentation. Also note that priority array setpoints were not kept on power loss.
13.3 BACNET
13.3.1 BACnet IP Connection
Connection of BACnet IP requires a physical cable connection to the RJ45 jack on the controller.
Prior to making the wiring connections, the controller is to be tested to verify proper control of
the DOAS unit under local control.
ETHERNET
CONNECTION