Programming User Established Alarm And Control Set Points
The LubriMist® Model IVT Oil Mist Generator is shipped with standard preset values for each of
the monitored variables. However user established control and alarm set points can be
established to meet particular operating needs.
All user established set points are made with the key pad located in the operator compartment.
. By pressing the [SET] and any <FUNCTION> key sequence any of the control or alarm
settings can be changed. Any number of operating variables may be changed, and they may be
addressed in any order. Exiting can be done at any time and will effect only those settings that
have been "entered" while in the program mode. Pressing the ENTER key logs a value into
memory.
The controller will only accept new values that are between the factory established high and low
settings. The programming mode therefore, allows the user to establish a narrower alarm band
around a set point within the minimum and maximum allowable values.
The following table lists the range within which the user can set limits to suit operating variables.
User Defined Set Point Ranges
Set Point Variable
US Units
Metric Units
Air Temperature - Control Set-point
100-150
°
F
38-65
°
C
Air Temperature - High Alarm Set-point
120-170
°
F
49-76
°
C
Air Temperature - Low Alarm Set-point
80-130
°
F
26-55
°
C
Air / Oil Heater - High Temperature Cutout Set-point
130-180
°
F
55-82
°
C
Supply Air Pressure - High Alarm Set-point
65-150 PSI
4.5-10.3 BAR
Supply Air Pressure - Low Alarm Set-point
25-75 PSI
1.7-5.2 BAR
Regulated Air Pressure - High Alarm Set-point
10-65 PSI
0.7-4.5 BAR
Regulated Air Pressure - Low Alarm Set-point
10-65 PSI
0.7-4.5 BAR
Supply Oil Pressure - High Alarm Set-point
130-150 PSI
9.0-10.3 BAR
Supply Oil Pressure - Low Alarm Set-point
1-100 PSI
0.1-6.9 BAR
Mist Pressure - High Alarm Set-point
30-60 In. H
2
0
75-150 m BAR
Mist Pressure - Low Alarm Set-point
10-25 In. H
2
0
25-62 m BAR
Mist Density - High Alarm Set-point
55-100 %
55-100 %
Mist Density - Low Alarm Set-point
10-50 %
10-50 %
Bulk Oil Reservoir Temperature - High Alarm Set-point
130-180
°
F
55-82
°
C
Bulk Oil Reservoir Temperature - Low Alarm Set-point
0-80
°
F
-17-27
°
C
Bulk Oil Reservoir Level - High Alarm Set-point
50-75 Gallons
189-284 Liter
Bulk Oil Reservoir Level - Low Alarm Set-point
10-25 Gallons
38-95 Liter
Air Pre-heater Temperature - Enable Set-point
15-40
°
F
-9-5
°
C
Air Pre-heater Temperature - Control Set-point
40-80
°
F
5-27
°
C
Air Pre-heater Temperature - High Alarm Set-point
60-90
°
F
16-32
°
C
Air Pre-heater Temperature - Low Alarm Set-point
20-50
°
F
-7-10
°
C
Air Pre-heater – High Temperature Cutout Set-point
80-100
°
F
27-38
°
C
To input a new set point, press the SET and appropriate key for the desired operating function.
The selected function will be displayed, giving the option to change the first variable or move to
the next. If the "ENTER" key is pressed, the previously displayed function set point is not
changed. Once the desired selection is made, use the “INC” and “DEC” keys to display the new
setting and press "ENTER". Once all set point variables have been entered for a <FUNCTION>,
the controller resumes normal run time operation.