LubriMist
®
Model IVT
Oil Mist Generating System
Installation and Operating Manual
Page 57
of 256
Terminal connections for the remote alarm contacts in the ATEX version of the Model IVT Oil Mist
Generator are located in a terminal enclosure located at the back of the IVT console cabinet.
A. To access the remote alarm contacts, find the two terminal enclosures mounted on the rear
of the IVT console cabinet. The terminals for connecting to the remote alarm are located in
the
lower enclosure
.
B. Locate the lower enclosure and remove the cover. Install the alarm wiring through the cable
connection, and connect to the proper terminals.
C. Close and secure the remote alarm circuit enclosure cover.
Take care to ensure that you are accessing the
correct enclosure. Failure to do so may result in
serious personal injury or damage to equipment
For ATEX Constructions,
Connect The Remote Alarm Wiring To Terminal
Numbers
1 - 2 - 3
1 - COM
2 - N.O.
3 - N.C.
Locate The Remote
Alarm Terminal Enclosure