LubriMist

®

 Model IVT 

Oil Mist Generating System 

Installation and Operating Manual 

(Series 201A) 

 
 
 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 

REVISION 18   
OCT 2020 
P/N 77740224 

Summary of Contents for LubriMist IVT

Page 1: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Series 201A REVISION 18 OCT 2020 P N 77740224...

Page 2: ..._______ ________________________________________________________________ ________________________________________________________________ ______________________________________________________________...

Page 3: ...er 31 Bulk Oil Reservoir Level Transmitter 32 Mist Pressure Transducer 32 Bulk Oil Reservoir Oil Temperature Sensor 32 Mist Density Sensor 33 Oil Supply Pressure Transducer 34 Auxiliary Oil Mist Gener...

Page 4: ...Red And Green External Status Lights 102 Event Log 103 Logged Alarm and Fault Messages 105 Logged Event Messages 106 REMOTE COMMUNICATION AND ALARM 107 Remote Alarm Contact 108 Serial Data Port RS 42...

Page 5: ...anel Wiring Diagram 230 VAC Supply Voltage IVT NEC Construction 184 Electrical Wiring Diagrams And Schematics IVT ATEX Construction 185 Ladder Diagram 115 VAC Supply Voltage IVT ATEX Construction 185...

Page 6: ...l 220 Sensitive Electronic Devices Caution Label 220 IVT Low Voltage Controller Layout 221 Component Identification 222 Thermocouple Input Output Terminal Strip TB1 TB2 223 4 20 mA Input Output Termin...

Page 7: ...ting System Installation and Operating Manual Page 7 of 256 Warm Ambient Option Cabinet Cooling NEC Construction 252 Warm Ambient Option Cabinet Cooling ATEX Construction 253 Optional Demisting Unit 2...

Page 8: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 8 of 256 INTRODUCTION...

Page 9: ...nd distribution of LubriMist Oil Mist is covered in other publications For additional information contact the manufacturing office nearest you or check our website For questions regarding this publica...

Page 10: ...void a hazard or personally injurious situation The SAFETY ALERT symbol is accompanied with other graphics to further identify the type of hazard or personal injury risk involved This symbol is used t...

Page 11: ...bol is used to indicate that a FORK TRUCK is used to transport the equipment The Fork truck operator should be properly trained in its operation and observe all plant driving and safety regulations Do...

Page 12: ...256 SYMBOL SYMBOL DESCRIPTION AND USE This symbol is used to advise the materials must be disposed of in accordance to environmental laws ordinances and directives Disposal methods which have ADVERSE...

Page 13: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 13 of 256 UNIT IDENTIFICATION AND LABELING...

Page 14: ...il Reclamation For installations using the patented LubriMist Closed Loop Oil Mist Systems The oil reclamation option includes equipment to reclaim the oil from the return mist header when closed loop...

Page 15: ...4 Gb IP56 ZONE 2 NOTE 2 E NEMA MOTOR 575 VAC 50 60 HZ 3 PHASE EXPLOSION PROOF CLASS 1 GROUP C D T3C NOTE 1 F MOTOR 250 VAC 50 HZ 1 PHASE EXPLOSION PROOF CLASS 1GROUP C D T3C NOTE 1 Cabinet Accessories...

Page 16: ...er Purchaser specifies the electrical power requirement Reference LubriMist Model IVT Model Code Designations For 115 VAC power____________________________ For 230 VAC power___________________________...

Page 17: ...nadian Standard for Industrial Control Equipment ANSI ISA 12 12 01 2012 Non Incendive Electrical Equipment for use in Class I Div 2 Hazardous Locations C22 2 No 213 M1987 Non Incendive Electrical Equi...

Page 18: ...to the product those changes are recorded as a change in Series Number This manual is for equipment entering the market as Series 201 A______ October 2007 201 A Volts AC Machinery is available for con...

Page 19: ...ng European Union Directives EU Directive 94 9 EC ATEX Directive EU Directive 2006 95 EC Low Voltage Directive LVD EU Directive 2004 108 EC Electromagnetic Compatibility Directive EMC The Manufacturer...

Page 20: ...on o Minimum allowable ambient with Cold Ambient Option air pre heater with cabinet heater to 40 C o Maximum allowable ambient with Warm Ambient Option cabinet cooling ATEX to 45 C Altitude to 2000m R...

Page 21: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 21 of 256 PRODUCT DESCRIPTION...

Page 22: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 22 of 256...

Page 23: ...location The INLET AIR SUPPLY MIST GENERATOR HEAD OIL SUPPLY INSTRUMENTATION AND ELECTRICAL and the AUXILIARY OIL MIST GENERATOR are all contained in the mechanical compartment located behind the oper...

Page 24: ...ower switches for the main oil mist generator and the auxiliary oil mist generator 6 Manual toggle valves for manually filling the main and auxiliary oil mist generator reservoirs 7 Mist pressure gaug...

Page 25: ...ree separate ball valves 3 The ball valves provide ON OFF control to a the main oil mist generator head b the oil supply pump or c the auxiliary oil mist generator head The air supply to each device h...

Page 26: ...the oil mist The generated oil mist exits the top of the IVT cabinet through a 2 pipe The mist outlet pipe is sealed as it exits the top of the IVT cabinet Mist Generator Head With Air Oil Heater The...

Page 27: ...ts the air oil heater manifold to function as a high temperature heater cutout The IVT controller maintains the air temperature of the main oil mist generator The controller produces a DC voltage outp...

Page 28: ...eceives a signal from a level switch when oil level drops to a determined level The controller then energizes a DC voltage solenoid operated air valve which in turn starts the pump The pump fills the...

Page 29: ...troller provides all monitoring and control functions Segregation of power voltage 30 VAC 60 VDC and control voltage 30 VAC 60 VDC is provided by separate enclosures All components in the power voltag...

Page 30: ...pressure alarm and low inlet air pressure alarm During operation the signal is used to provide an operating inlet air pressure value Ambient Air Temperature Sensor The ambient air temperature is monit...

Page 31: ...system has been commissioned only minor adjustments to the regulated air pressure is needed to maintain proper system operation The regulated air pressure transducer is located on the main oil mist ge...

Page 32: ...nch proportional to the spacing of the sensor switches The level transmitter is connected to the IVT controller with a flexible cord Through the controller the level transmitter monitors the level in...

Page 33: ...a quantitative oil air ratio the LubriMist monitor does not make a mass measurement of the amount of oil suspended in the air The out put signal range of 0 100 percent mist density represents a change...

Page 34: ...s that pump operation has started When the oil transfer pump is cycling its operation is monitored The oil pressure transducer is mounted in a manifold at the oil pump outlet It is a two wire 4 20 mA...

Page 35: ...closure Distribution from the terminal strip is made to power the controller and heater element The controller produces a DC voltage output signal to a solid state non arcing relay for switching power...

Page 36: ...use when using LubriMist Closed Loop technologies 2 Warm Ambient Option is for use in hot ambient climates 3 Air Purge for use in aggressive or highly corrosive environments 4 Cold Ambient Option is...

Page 37: ...of the reservoir This connection allows oil to be drained away should the reservoir be overfilled It is located above the high level switch position The Oil Mist Reclamation unit is a self contained...

Page 38: ...factory set and nonadjustable Each cooling cycle starts when the internal operating temperature reaches approximately 124 F 51 C and remains on until the temperature in the controller enclosure is re...

Page 39: ...is controlled at approximately 32 C 90 F The thermostat is factory set The IVT Oil Mist Generator Cabinet Cooling system for the ATEX construction includes the vortex cold air generator with temperatu...

Page 40: ...or of the IVT Controller enclosure The IVT Oil Mist Generator Controller Air Purge Assembly includes an air purge meter rotometer and supply air block valve Spent air is exhausted through an enclosure...

Page 41: ...upply A sensor at the inlet of the heater senses the inlet air temperature When the inlet air temperature falls below 40 F 5 C the pre heater is activated The discharge temperature from the pre heater...

Page 42: ...chanical compartment and the other inside of the operator interface compartment Each is controlled by separate thermostats Thermostats are set to turn the heaters ON when the internal cabinet temperat...

Page 43: ...temperatures are maintained at the oil mist generator The pre heater is installed in the incoming air supply A sensor at the inlet of the heater senses the inlet air temperature When the inlet air te...

Page 44: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 44 of 256 Cold Ambient Option Air Preheating ATEX constructions...

Page 45: ...diators heaters warm the internal cabinet spaces one is located in the mechanical compartment and the other inside of the operator interface compartment Each has an integral thermostat to control the...

Page 46: ...e IVT A shut off valve is provided for servicing a 10 micron spin on type oil filter Supply oil pressure can be observed via a 0 300 PSI 0 21 Bar pressure gauge The bulk oil reservoir level is continu...

Page 47: ...uctions must be installed in accordance with the requirements of BS EN60079 14 1997 Part 14 Electrical installations in hazardous areas other than mines WARNING THIS INSTRUMENT MUST BE EARTHED WARNING...

Page 48: ...r access is maintained at the front of the unit when the cabinet door is open for system operation and ease of access to the disconnect switch located in the front operating compartment See the sectio...

Page 49: ...0 lb RF Flange located at the right rear of the unit When threaded flanges are use to connect to the header system do not use Teflon tape or conventional pipe dope A non hardening thread lubricant suc...

Page 50: ...M3 Hr 213 BI 1 75 6 40 SCFM 2 97 10 87 M3 Hr 475 BI 2 48 14 30 SCFM 4 21 24 30 M3 Hr 933 BI 5 70 28 0 SCFM 9 68 47 57 M3 Hr IVT Mist Generator Size Minimum Recommended Air Supply Capacity US Units Met...

Page 51: ...elow for terminal enclosure location and user terminal connection identification The power connection for the IVT oil mist generator is single phase Voltage is as specified on the equipment nameplate...

Page 52: ...4 ATEX Equipment 3G Ex nA nL nC IIC T4 Without Cold Ambient Option With Cold Ambient Option Without Cold Ambient Option With Cold Ambient Option 115 15 5 Amperes 23 Amperes 8 1 Amperes N A 230 7 8 Amp...

Page 53: ...t Heater Option Cabinet heaters installed in IVT oil mist generators buit to the NEC electrical option must be connected to a separate power source Connections are made at the powere switch located on...

Page 54: ...USTOMER CIRCUIT GROUND CONNECTION CONNECT GROUND CONDUCTOR TO GROUND TERMINAL CIRCUIT GROUND CONNECTION NEC CONSTRUCTION ACCESS FROM RIGHT SIDE CIRCUIT GROUND CONNECTION ATEX CONSTRUCTION ACCESS FROM...

Page 55: ...o provide remote monitoring by either of two methods 1 A basic ON OFF closure from the dry FORM C contact can be connected to a user sourced alarm 2 An RS 422 485 serial connection is available for da...

Page 56: ...compartment and located above the reservoir are two electrical control enclosures The electrical enclosure located to the left is the AC power enclosure Conduit is provided inside the mechanical compa...

Page 57: ...T console cabinet The terminals for connecting to the remote alarm are located in the lower enclosure B Locate the lower enclosure and remove the cover Install the alarm wiring through the cable conne...

Page 58: ...ol enclosures The electrical enclosure located to the right is the controller enclosure Conduit is provided inside the mechanical compartment for the users wiring The conduit connects the external rem...

Page 59: ...rear of the IVT console cabinet The terminals for connecting to the remote alarm are located in the lower enclosure 2 Locate the lower enclosure and remove the cover Install the alarm wiring through t...

Page 60: ...also equipped with a high level switch The high level switch is wired to the main oil mist generator controller and provides a local and unit alarm should a high level condition occur When a high leve...

Page 61: ...termine specific motor power requirements b High level output terminals for the port in the NEC version of the Model IVT Oil Mist Generator are located in the low voltage controller enclosure To acces...

Page 62: ...r occurs A user furnished local emergency disconnect switch should also be installed adjacent to the oil mist reclamation unit a Power connection to the electric motor is made at the motor terminal en...

Page 63: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 63 of 256...

Page 64: ...re to have flash points greater than 200 F 93 C NOTICE For IVT Oil Mist Generators equipped with either the Warm Ambient Option Cabinet cooling or Cold Ambient Option Air Preheating and Cabinet Heatin...

Page 65: ...nected to the reservoir with a chain to discourage misplacing c Check the end of the oil fill hose for contamination Clean away any dirt and grit that may be in or on the hose end nozzle Insert the ho...

Page 66: ...ressure regulator set the pump cycle speed between 160 and 200 cycles per minute Maximum oil fill rate to the main oil mist generator is at 200 cycles per minute Once the pump speed has been set relea...

Page 67: ...perator compartment Locate and open the air block valves to the main oil mist generator Valves are open when the handles are rotated to the full clock wise position Note that when the air supply is op...

Page 68: ...ntrol level switch The air solenoid valve then de energized once the level rises to the normal operating oil level A fixed position level switch located in the main oil mist generator reservoir mainta...

Page 69: ...red and normal operating conditions are maintained use the CLEAR key on the control panel keypad to put the IVT Oil Mist Generator into the normal operating mode Press the CLEAR key once to clear each...

Page 70: ...n alarm set points This period allows the oil output to stabilize and the mist sensor internal surfaces to become wetted with oil Since the mist sensor does not measure the absolute quantity of oil in...

Page 71: ...IVT Oil Mist Generating System Installation and Operating Manual Page 71 of 256 1 Low Mist Sensitivity Range 2 Mid Mist Sensitivity Range 3 High Mist Sensitivity Range 4 Power To LED Array OFF Positi...

Page 72: ...is properly installed and connected to the return mist connection Check the oil reclamation unit reservoir drain valve and ensure that it is closed and the drain plug is secure Open the air supply bl...

Page 73: ...f 256 Start Electric Motor Drive Use Pressure Regulator To Adjust Air Supply Pressure To The Transfer Pump Air Pressure Gauge Monitors Pressure To Transfer Pump Open Air Supply Valve To Oil Reclamatio...

Page 74: ...pins set at 180 apart The damper position is locked and secured in position by lock nuts on each pin The damper position is indicated by the orientation of the screwdriver slot in the end of the pins...

Page 75: ...or has been commissioned and operating so that the air supply block valve to the IVT is in the full open position B Open the air supply block valve to the IVT Oil Mist Generator cabinet cooling system...

Page 76: ...r pressure Adjust the air pressure regulator to 4 8 5 2 Bar 60 75 PSI B Turn the electrical power switch to the ON position If the temperature inside of the cabinet is greater than approximately 32C 9...

Page 77: ...enerating System Installation and Operating Manual Page 77 of 256 10 10 9 8 8 9 11 11 7 7 4 3 2 1 G 5 5 G 1 2 3 4 6 6 Turn the Electrical Power Switch to the ON position Open Air Supply Block Valve Ch...

Page 78: ...in the full open position B Open the air supply block valve to the IVT Oil Mist Generator air purge system C Locate the airflow needle valve located at the base of the rotometer Adjust the needle val...

Page 79: ...t Turn the electrical power switch to the ON position If the temperature inside of the cabinet is less than 10 C 50 F the heaters will energize and begin warming the cabinet interior B Find the thermo...

Page 80: ...Open the oil supply block valve to the IVT Oil Mist Generator auto bulk oil fill system D Open left cabinet door to the IVT Locate the oil supply pressure gauge located next to the solenoid operated o...

Page 81: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 81 of 256 OPERATING GUIDE...

Page 82: ...ted as either in Alarm or Normal condition Keypad Buttons The 16 buttons located on the operator interface keypad perform the following functions AIR TEMP When depressed this key displays in real time...

Page 83: ...rrecting an alarm condition Pressing the CLEAR key once clears an alarm Pressing the CLEAR key a second time clears the overhead status lights from red to green TIME When depressed this key displays t...

Page 84: ...be under the day a use the INC and DEC keys to adjust Once finished b press ENTER key 4 The display will read SET DATE DATE Program cursor will be under the date a use the INC and DEC keys to adjust...

Page 85: ...and minutes are settable Seconds are recorded to ensure proper chronological ordering of events 3 The display will read SET TIME HOURS Program cursor will be under the hour value a use the INC and DE...

Page 86: ...conditions of each operating variable can be prompted Simply by pressing any system function key the operating variable and its current value will be displayed 2 Operating Condition And Value Is disp...

Page 87: ...sure Low Alarm Set point 10 In H2 0 25 m BAR Mist Density High Alarm Set point 90 90 Mist Density Low Alarm Set point 10 10 Bulk Oil Reservoir Temperature High Alarm Set point 160 F 71 C Bulk Oil Rese...

Page 88: ...y Air Pressure High Alarm Set point 65 150 PSI 4 5 10 3 BAR Supply Air Pressure Low Alarm Set point 25 75 PSI 1 7 5 2 BAR Regulated Air Pressure High Alarm Set point 10 65 PSI 0 7 4 5 BAR Regulated Ai...

Page 89: ...y sequence The following illustrations assume that key sequences are initiated and completed while the unit is operating normally This symbol is used to indicate that an operating variable or message...

Page 90: ...NT PRESS ENTER KEY SET AIR HEATER LOW TEMP XXX SET POINT CORRECT PRESS INC DEC KEY TO ACHIEVE SET POINT PRESS ENTER KEY SET AIR HEATER CUT OUT TEMP XXX SET POINT CORRECT PRESS INC DEC KEY TO ACHIEVE S...

Page 91: ...POINT CORRECT PRESS INC DEC KEY TO ACHIEVE SET POINT PRESS ENTER KEY SET PREHEATER START TEMP XXX SET POINT CORRECT PRESS INC DEC KEY TO ACHIEVE SET POINT PRESS ENTER KEY YES YES YES NO NO YES NO SET...

Page 92: ...END NOTE Set Point change are not saved if the CLEAR key is pressed during the key sequence The key sequence must be completed in order and in its entirety for changes in set points to be established...

Page 93: ...IR TEMP Displays Inlet Air Supply Temperature with Air Pre Heater option only SET SET CLEAR Clears the EVENT LOG SET SET DATE Clears the DATA LOG SET SET TIME Displays Number of DATA Entries In Memory...

Page 94: ...Press SET SET INC The IVT displays the communications event count After three seconds the IVT displays the return bus message count After three seconds the IVT displays the return bus communication e...

Page 95: ...st the display contrast press the key sequence SET while the IVT is operating in the normal Run Time mode The screen below will be displayed Now use the to increase the text contrast and to decrease t...

Page 96: ...ce must be completed in order and in its entirety for changes to be established 1a Press SET ENTER The display prompts to enter a unique unit number for the IVT oil mist generator If only one IVT is c...

Page 97: ...9600 bps Use the INC and DEC keys to select among the available speeds 300 1200 2400 4800 9600 or 19200 The default setting is 9600 bps 2a Press ENTER The Serial Speed selection is saved Thermocouples...

Page 98: ...ion calibration feature use the INC and DEC keys to toggle between YES and NO The default setting is NO Yes Enabled NO Disabled 3a Press ENTER IVT controller has a feature to discourage easy access to...

Page 99: ...ting is made at the factory prior to shipment Use the INC and DEC keys to toggle between Yes and No 6a Press ENTER This control specifies whether customer established alarm set points and control sett...

Page 100: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page100 of 256 8 Press ENTER Communication and option feature set up is complete LOCAL ALARMS INDICATORS AND READOUT...

Page 101: ...4 11 High Oil Level De misting Reservoir 4 12 Air Pre heater Temperature 4 The signal from the level switch and nine standard two optional sensors is fed into conditioning circuits of the controller...

Page 102: ...nd normal operation resumes the display will continue to identify the alarm until the display is cleared This feature is very important in identifying trouble alarms that may fluctuate between normal...

Page 103: ...bulk oil reservoir To access the EVENT LOG use the following key sequence routine The INC and DEC keys can be used to quickly scroll through the events in order of their occurrence When there is no da...

Page 104: ...ure GG Mist Pressure HH Mist Density Press ENTER again Pressing the ENTER key returns the screen to the event identification screen Using the ENTER key displays in circular order the event identificat...

Page 105: ...Regulated Pressure Regulated Air Pressure Low Alarm Low Regulated Pressure Supply Oil Pressure High Alarm High Oil Supply Pressure Supply Oil Pressure Low Alarm Low Oil Supply Pressure Mist Pressure...

Page 106: ...ens last for 5 seconds once an event occurs and Run Time screen is then restored Event Display Top Line Display Bottom Line Unit Powered On or Reset Unit Powered On or Reset Clock changed from keypad...

Page 107: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page107 of 256 REMOTE COMMUNICATION AND ALARM...

Page 108: ...alarm enunciator The relay contact is part of the same hermetically sealed relay that operates the red and green unit status lights Each time the unit status lights operate so do the remote alarm con...

Page 109: ...m Connections in the INSTALLATION section of this manual for terminal location and connection information This data port conforms to EIA 485 A and EIA 422 B specifications for balanced data transmissi...

Page 110: ...SERVER COMMUNICATON PORT 4 WIRE CONFIGURATION T X T X R X R X OIL MIST GENERATOR COMMUNICATON PORT R X R X T X T X MODEL IVT COMMUNICATON PORT OIL MIST GENERATOR T X T X R X R X MODEL IVT Connecting...

Page 111: ...422 485 terminal locations see Remote Communication And Alarm Connections in the section titled INSTALLATION of this manual PERSONAL COMPUTER PERSONAL COMPUTER R X R X T X T X R X R X T X T X NON HAZA...

Page 112: ...p The event log is also accessible the serial data port For additional information see Event Log in the section titled LOCAL ALARMS INDICATORS AND READOUT The IVT data communication port transmits an...

Page 113: ...ew connection This connection should be descriptive to the area where your IVT is installed Hyper terminal will also ask you to choose an icon for your connection name Once a file name and icon have b...

Page 114: ...Select Direct to COM1 COM2 or COM3 depending on which communication port you are connected to 4 Hyper terminal will now setup the communication port Make the following selections as listed below Bits...

Page 115: ...s now set up to receive the EVENT LOG and the DATA LOG for the IVT Oil Mist Generator NOTICE It is recommended that the connection setup be saved prior to importing data from the IVT Oil Mist Generato...

Page 116: ...he bottom of the screen will turn bold The EVENT LOG and the DATA LOG can now be transferred from the IVT Oil Mist Generator to the PC 8 From the PC keyboard select the E key to view the EVENT LOG To...

Page 117: ...rating Manual Page117 of 256 The captured LOG is now saved in the file named at STEP 6 and can be imported into different program formats for dissemination Repeat STEPS 6 through 8 to capture separate...

Page 118: ...sophisticated and automatic way with a supervisory or monitoring host computer Modbus is a master slave system The IVT is designed to act as a slave with the host computer acting as the master The ho...

Page 119: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page119 of 256 Connecting To The Host Computer via 4 wire Figure 1 Connecting To The Host Computer via 2 wire Figure 2...

Page 120: ...ired use the INC and DEC keys to set the Modbus slave address from 1 to 247 Press the ENTER key to save the address 4 The Modbus Transmission Mode should now be displayed RTU and ASCII If it is not as...

Page 121: ...a The device ID s parameters are 1 to 247 b The IVT s parameters are 001 to 247 Note 001 is the same as 1 2 To set the rest of the parameters in the Modscan screen click the connection button in the...

Page 122: ...tion Code and it s HEX Addresses 2 Viewing the IVT s values in real time Before number 1 can be analyzed below is a brief description on the Function Codes and the HEX Addresses Function Codes There a...

Page 123: ...o 0 and 1 is added to the next place value so 10 would be 16 and so on The original designers of Modbus used 1 as the starting value of Coils Inputs and Registers reserving 0 for another use That is w...

Page 124: ...determine which values or parameters will be viewed This is where the function code shows up in the message frame 3 Data sent will consist of 2 sets of data 00 00 00 01 the first two sets of numbers...

Page 125: ...ing polled The status of the address being polled doesn t necessarily mean it is going to come back in the form of a 1 or 0 on or off It can also come back in the form of Odd or Even but break down th...

Page 126: ...f digital output 6 07 06 Not Used 08 07 Mist Tank Oil Level Sensor Switch 09 08 Mist Tank Low Oil Level Sensor Switch 0a 09 De Mist Tank High Oil Level Message frame being received Input Status Functi...

Page 127: ...off It can also come back in the form of Odd or Even but break down those numbers in binary form and they will be 1 or 0 From the IVT here s how it breaks down The status of components in the Input S...

Page 128: ...ss in the Modscan screen address hex box See Holding Register addresses below The second set of numbers 00 01 are the length In Function Code 03 the length can have up to 24 polling places which will...

Page 129: ...code 03 Refers to the setpoints from the IVT 01 03 02 07 cf fa 20 1 Device I D in Modscan screen has to be the same as the IVT location 2 In the Modscan screen Modbus point type Function code are the...

Page 130: ...code 04 below for this example an erroneous value of 65078 for the Air Pre heater Enable temp would be given By using Address HEX 0002 Bulk Oil Reservoir Level a reasonable value can be ascertained Me...

Page 131: ...ed 4 Cyclical Redundancy Checking or CRC 01 04 02 00 44 b9 03 The first two sets of numbers are the same as the previous 1 The device ID 01 2 The Function code 04 3 Data Received Has 3 sets of numbers...

Page 132: ...n screen Refer to figure 6 Figure 6 Note the Show data and the Integer buttons can also be established from the menu bar Click setup and then highlight Display Options then place a check mark next to...

Page 133: ...nput Status is transmitted in what is sometimes called a packed bit format This refers to the fact that the individual status values are packed into the individual bits of a larger 16 bit data word Sp...

Page 134: ...gh this representation may appear strange at first it is useful and numerically correct because simple addition and subtraction yield correct results and it is the most commonly used format for that r...

Page 135: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page135 of 256 BULK OIL SUPPLY RESERVOIR...

Page 136: ...interfaced with the IVT controller Additional information on read outs and remote monitoring can be found elsewhere in this manual Commission The Auxiliary Oil Mist Generator Before oil can be added...

Page 137: ...ling is complete remove the oil supply hose and reinstall the oil fill cap The cap is threaded and seals with an o ring Care should be taken to ensure proper thread alignment and engagement The cap ne...

Page 138: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page138 of 256 AUXILIARY OIL MIST GENERATOR...

Page 139: ...pressure and reservoir oil level gauges are provided to locally monitor the mist pressure and reservoir oil level once the unit has been placed into operation A plugged reservoir drain valve is provi...

Page 140: ...valve located toward the left supplies air pressure to the oil transfer pump The toggle valve located on the right opens the pump discharge to the auxiliary oil mist generator reservoir Open and hold...

Page 141: ...lector switch to the center position I O II 3 Turn OFF the air supply to the main oil mist generator a Adjust the air pressure regulator to the closed position Turning the adjustment knob on the air p...

Page 142: ...e auxiliary oil mist generator switch is located on the right side Move the switch to the ON position b For ATEX configured units power is supplied through a three position selector switch To turn pow...

Page 143: ...tput SSR2 will be ON If the temperature of the 2 thermocouple is above the programmed cutoff Set point SSR2 will be OFF If the temperature of thermocouple 2 falls below the programmed Low Alarm Set po...

Page 144: ...will display 3 The UP and DOWN arrow keys will adjust the alarm setpoint between the limits of 60F and 100F or equivalent degrees C if F C Jumper is ON Pushing SET again will advance to the next param...

Page 145: ...re will bleed to zero b Close the air supply block valve to the auxiliary oil mist generator 3 Commission the main oil mist generator as described in the section titled COMMISSIONING in this manual Mi...

Page 146: ...ir pressure signal down stream of the valve increases to the supply pressure setting 150 PSI maximum Air pressure is applied to the bottom of the main air cylinder moving the valve poppet UP thus open...

Page 147: ...GULATOR MIST OUTLET FROM AUXILIARY UNIT MIST OUTLET INLET AIR 3 If the block valves to both oil mist generators are inadvertently placed in the open position at the same time because the supply air pr...

Page 148: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page148 of 256...

Page 149: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page149 of 256 CONTROLLING THE MIST...

Page 150: ...nerators 2 The AIR OIL HEATER controls the temperature of the oil as it is being converted from a liquid into oil mist particles Because oil viscosity has a definite influence on oil mist generation i...

Page 151: ...g it counter clockwise more air will be added to the oil mist leaving the generator This essentially dilutes the air oil ratio by adding more air Without reducing the regulated air pressure setting ad...

Page 152: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page152 of 256...

Page 153: ...ail For ATEX Model IVT in the UNIT IDENTIFICATION AND LABELING section of this manual for additional information Mist Generator Size Mist Generating Range Number Of Machined Groves In Vortex Plate US...

Page 154: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page154 of 256 ROUTINE MAINTENANCE NOTICE Only a qualified person should make replacement of spare parts...

Page 155: ...L MIST GENERATOR CHECKS a Check mist header pressure setting 20 inches H2O 50 m BAR b Check low mist pressure alarm setting Factory setting is 10 inches H2O 25 m BAR c Check high mist pressure alarm s...

Page 156: ...ter element P N 77780352 d Inspect and thoroughly clean the interior of the oil mist generator reservoirs e Check and verify operation of the high and low set points of all alarms f Check the operatio...

Page 157: ...free rags for cleaning and wiping them out The outside and interior of the IVT cabinet and reservoir may be wiped down with cloth rags or recyclable paper wipes or towels that are able to absorb oil a...

Page 158: ...onmental effect any used cleaning agents used and plan your cleanup accordingly Use environmentally friendly products and recycle where ever possible Ensure that decontamination or cleaning agents use...

Page 159: ...from the bulk oil reservoir the main oil mist generator reservoir and the auxiliary oil mist generator reservoir If the IVT includes an oil reclamation system for Closed Loop Systems the oil reclamat...

Page 160: ...e IVT using a fork truck Slot dimensions are 8 w x 4 h or 222 mm x 100 mm Unbolt the machine form its foundation to remove Do not tip or stand equipment on edge Use a fork truck or similar suitable tr...

Page 161: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page161 of 256 TROUBLE SHOOTING GUIDE...

Page 162: ...possible solution If the alarm condition still exists the severity of the alarm or problem may be beyond the possible solutions listed in this guide Please contact manufacture 800 800 5823 for further...

Page 163: ...se resulting in a decrease in mist production 4 Confirm mist head oil flow valve has not been adjusted further than 3 turns See mist head adjustment screw locations below Closing the oil flow valve in...

Page 164: ...mal operating mode 2 If the mist pressure is near the Low Alarm Setting 10in H2O 25mBar check the oil mist header systems for broken mist lines or pipes and IVT oil mist generator for leaks 3 Verify t...

Page 165: ...n how to access the event log If it is determined that the regulated air pressure has been changed and that the High Mist Pressure alarm is due the change in regulated air pressure correct the setting...

Page 166: ...air pressure has been changed and no occurrence of a High Mist Pressure is recorded then the setting may be corrected Increase the regulated air pressure to achieve 20in H2O oil mist pressure If regul...

Page 167: ...sure does not change with adjustments to air regulator The air regulator is defective and should be replaced CFH RS part no 77700501 If a Low Mist Pressure alarm is recorded in the Event Log then it p...

Page 168: ...power is being applied to the air heater element Confirm whether the LED is lit while the air temperature is below the control set point 5 If relay LED is on and air temperature is not increasing chec...

Page 169: ...itch mist generation to Auxiliary See procedure located on interior of IVT cabinet door LOW OIL LEVEL MIST TANK LEVEL Oil Level within mist generating tank is below low alarm point Normally this alarm...

Page 170: ...utoff alarm is designed to act as a failsafe feature for the Air Heater Element The temperature sensor that controls the high air cutoff alarm is separate from the sensor used to control air temperatu...

Page 171: ...sition The air toggle valve is located on the front operator panel Replace pump if necessary CFH RS part number 77780134 7 If repair is not possible switch mist generation to Auxiliary See procedure l...

Page 172: ...um regulated air pressure is 10 PSI Increase pressure above interlock setting 10PSI 69BAR The IVT Auxiliary Controller will not permit the air heater element to energized if the regulated air pressure...

Page 173: ...he regulated air pressure reading press the Reg Air Pres key If the regulated air pressure is less that 10 PSI 0 69 BAR increase the pressure above the low alarm setting See Troubleshooting solutions...

Page 174: ...lace the SSR 2 relay if the green LED remains ON CFH RS part number 77780152 HIGH PREHTR CUTOFF AIR TEMPERATURE Heated Pre Heater Air Temperature is above High Cutoff Alarm Setting 100 F 38 C 1 Press...

Page 175: ...nual Page175 of 256 IVT Ambient Conditioners 40 20 0 20 40 60 80 100 120 140 0 5 10 15 20 25 30 Mist Flow SCFM Ambient Temp F Amb 4F 20C Cabinet Heating Req ired Ambient 120F 50C Cabinet Cooler R d NE...

Page 176: ...ting Manual Page176 of 256 PARTS LIST DRAWINGS SCHEMATICS EXPLOSION HAZARD Substitution of components may impair suitability for II 3G Ex ic nA nC db eb mb IIC T4 WARNING EXPLOSION HAZARD Substitution...

Page 177: ...26 Relay 24VDC Coil 10A 240V Contacts 1 2 3 4 4 5 5 6 6 7 7 2 77780111 Gauge Oil Level 8 Long Alum 2 4 6 8 9 10 11 12 13 13 14 2 77780119 Cylinder Air Switching Valve 2 4 6 8 9 10 11 12 13 13 14 2 777...

Page 178: ...142 RTD 1 4 OD x 4 Lg 1 1 77780143 Low Pressure Switch Adj 8 60PSIG Set 10 PSI Decreasing 1 1 77781469 Temperature Heater controller PID 1 1 77780145 Oil Level Switch Dual Floats 1 1 77780148 Thermoco...

Page 179: ...NG PRESSURE PRESSURE TRANSDUCER MIST PRESSURE AIR PRESSURE REGULATOR AUXILIARY UNIT AIR OIL HEATER MAIN OIL MIST GENERATOR AIR PRESSURE REGULATOR MAIN UNIT AIR PRESSURE INDICATOR 0 100 PSI 0 6 9 BAR G...

Page 180: ...SENSOR H3 AIR PREHEATER TT TEMPERATURE CONTROL H3 AIR PREHEATER TC TEMPERATURE SENSOR H 3 AIR PRE HEATER CUT OUT TC AIR PRESSURE REGULATOR AIR COOLER OIL LEVEL GAUGE AUXILIARY MIST TANK OIL LEVEL GAUG...

Page 181: ...TROLLER 16 4 NC 17 3 1 C NO 6 5 C 8 1 3 2 FAULT NORMAL R G XL 1 13 1A XL 2 9 OPTIONAL EQUIPMENT EC 2 S S POWER SUPPLY OPTIONAL EQUIPMENT RELAY 25A OUTPUT RELAY 25A RELAY 25A S S S S BU SSR 2 BU SSR 1...

Page 182: ...R SWITCH 10 POWER SWITCH MAIN UNIT OFF ON 6 INCOMING POWER 115 VAC 1PH 2L1 2L2 1L2 1L1 6 H 1 5 7 H 3 16 4 9 17 G R XL 1 XL 2 MAIN UNIT AC POWER ELECTRICAL PANEL SSR 1 SSR 2 AUXILIARY UNIT ELECTRICAL P...

Page 183: ...1 MAIN UNIT ELECTRONIC CONTROLLER FAULT NORMAL OPTIONAL EQUIPMENT EC 2 S S POWER SUPPLY OPTIONAL EQUIPMENT RELAY 25A OUTPUT RELAY 25A RELAY 25A S S S S BU SSR 2 BU SSR 1 OUTPUT OUTPUT RELAY 25A SSR 1...

Page 184: ...IN UNIT OFF ON 6 INCOMING POWER 115 VAC 1PH 2L1 2L2 1L2 1L1 HEATER OPTIONAL EQUIP AIR PREHEATER LOCAL UNIT STATUS LIGHTS 6 H 1 5 7 H 3 16 4 9 17 AIR OIL G R XL 1 XL 2 MAIN UNIT AC POWER ELECTRICAL PAN...

Page 185: ...UNIT ELECTRONIC CONTROLLER FAULT NORMAL OUTPUT S S SSR 1 RELAY 25A OUTPUT OUTPUT BU SSR 1 BU SSR 2 S S EC 2 S S RELAY 25A RELAY 25A AUXILIARY UNIT ELECTRONIC CONTROLLER AIR PREHEATER NOT AVAILABLE 4...

Page 186: ...TB 1 TB 2 TX TX DC VOLTAGE COMPONENTS SERIAL DATA PORT RS 422 485 RX RX TX TX DO 4 DO 4 TX RX TX RX RX RX DO 4 TX TX DO 4 TO DO 4 FOR DEMISTING MOTOR INTERLOCK DO 4 DO 4 TB8 8 11 10 9 TB5 3 3 SOLID ST...

Page 187: ...TOR SWITCH CONTROLLER ELECTRONIC MAIN UNIT EC 1 CUSTOMER CONNECTIONS REMOTE ALARM CONTACTS 120mA 28VDC UY 1 SEALED RELAY HERMETICALLY UY 1 10A NORMAL FAULT 12 4A 4 10A 10 H 1 H 2 IVT AUXILIARY UNIT 3...

Page 188: ...B 2 TX TX DC VOLTAGE COMPONENTS SERIAL DATA PORT RS 422 485 RX RX TX TX DO 4 DO 4 TX RX TX RX RX RX DO 4 TX TX DO 4 TO DO 4 FOR DEMISTING MOTOR INTERLOCK DO 4 DO 4 TB8 8 11 10 9 TB5 3 3 SOLID STATE TB...

Page 189: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 189 of 256 Electrical Wiring Schematic Cold Ambient Option Cabinet Heating 115 or 230 VAC NEC Construction Only...

Page 190: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 190 of 256 Electrical Wiring Diagram Cold Ambient Option Cabinet Heating 115 or 230 VAC NEC Construction Only...

Page 191: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 191 of 256 Voltage Panel Wiring Diagram Warm Ambient Option Cabinet Cooling 115 or 230 VAC ATEX Construction Only...

Page 192: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 192 of 256 Voltage Panel Wiring Diagram Cold Ambient Option Cabinet heating 230 VAC ATEX Construction Only...

Page 193: ...roller Wiring Connection Detail AUXILIARY UNIT ELECTRONIC CONTROLLER EC 2 BU SSR 2 BU SSR 1 THERMOCOUPLE TYPE K MIST HEAD HIGH AIR TEMP THERMOCOUPLE TYPE K MIST HEAD AIR TEMP AIR OIL HEATER RELAY HIGH...

Page 194: ...ter Mechanical Compartment 1 8 Amperes 0 9 Amperes Auxiliary Oil Mist Generator Air Oil Heater 850 watts 7 4 Amperes 3 7 Amperes Electronic Controller 40mA 40mA ATEX Constructions Description Full Loa...

Page 195: ...t corrective actions and maintenance actions have been initiated and completed and the original cause of the fuse failure has been corrected Reference the electrical wiring diagrams located in this se...

Page 196: ...Model IVT Oil Mist Generating System Installation and Operating Manual Page 196 of 256 FUSE TERMINAL LOCATION MAIN OMG FUSE LEGEND 115VAC IVT MAIN OIL MIST CONSOLE FUSE LEGEND 230VAC IVT MAIN OIL MIS...

Page 197: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 197 of 256 Fuse Legend 115 VAC Main Oil Mist Generator...

Page 198: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 198 of 256 FUSE LEGEND 115VAC IVT MAIN OIL MIST CONSOLE...

Page 199: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 199 of 256 Fuse Legend 230 VAC Main Oil Mist Generator FUSE LEGEND 230VAC IVT MAIN OIL MIST CONSOLE...

Page 200: ...m Installation and Operating Manual Page 200 of 256 Fuse Location Auxiliary Oil Mist Generator FUSE LEGEND 115VAC IVT AUXILIARY OIL MIST CONSOLE FUSE LEGEND 230VAC IVT AUXILIARY OIL MIST CONSOLE A A V...

Page 201: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 201 of 256 Fuse Legend 115 VAC Auxiliary Oil Mist Generator FUSE LEGEND 115VAC IVT AUXILIARY OIL MIST CONSOLE...

Page 202: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 202 of 256 Fuse Legend 230 VAC Auxiliary Oil Mist Generator FUSE LEGEND 230VAC IVT AUXILIARY OIL MIST CONSOLE...

Page 203: ...nd Operating Manual Page 203 of 256 Tagging and Labeling Standard equipment tags and labels are shown in the following diagrams Additional special equipment tagging or identification labels not shown...

Page 204: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 204 of 256 IVT Front Cabinet Door...

Page 205: ...f 256 IVT Operator Access Compartment IMPORTANT DO NOT FILL OIL WITHOUT FIRST COMPLETING THE FOLLOWING STEPS 1 2 3 4 5 EMPTY ALL COLLECTION CONTAINERS EMPTY ALL DRAIN LEGS WAIT 4 HOURS FOR OIL TO RETU...

Page 206: ...TIC ELECTROMAGNETIC MAGNETIC OR RADIOACTIVE FIELDS CAUTION Sensitive Electronic Devices DO NOT SHIP OR STORE NEAR STRONG ELECTROSTATIC ELECTROMAGNETIC MAGNETIC OR RADIOACTIVE FIELDS SENSITIVE ELECTRON...

Page 207: ...D 115VAC IVT AUXILIARY OIL MIST CONSOLE OR 5 11 10 9 8 7 6 4 3 2 1 G WARNING 77500601 WARNING LABEL WARNING FUSE LEGEND 230VAC IVT AUXILIARY OIL MIST CONSOLE 77780293 WARNING LABEL 77780293 WARNING LA...

Page 208: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 208 of 256 IVT Cabinet Rear...

Page 209: ...et temperature This device should not be operated when the internal temperature is greater than 40 C Ensure that the cabinet cooling system is properly operating and that the internal cabinet temperat...

Page 210: ...erating instructions for further detail WARNING The IVT Oil Mist Generator is equipped with a cabinet heating system for maintaining minimum internal cabinet temperature operating condition This devic...

Page 211: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 211 of 256 Tag Details 77500601 Warning Label WARNING 77500603 Remote Alarm Contact Rating Label 120Ma 24 VDC...

Page 212: ...ing System Installation and Operating Manual Page 212 of 256 77780286 Fuse Legend 115 VAC Aux Unit FUSE LEGEND 115VAC IVT AUXILIARY OIL MIST CONSOLE 77780287 Fuse Legend 230 VAC Aux Unit FUSE LEGEND 2...

Page 213: ...erating System Installation and Operating Manual Page 213 of 256 77780288 Fuse Legend 115 VAC Main Unit FUSE LEGEND 115VAC IVT MAIN OIL MIST CONSOLE 77780289 Fuse Legend 230 VAC Main Unit FUSE LEGEND...

Page 214: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 214 of 256 77780290 NEC NAMEPLATE 77780291 ATEX Nameplate...

Page 215: ...Page 215 of 256 77780293 Warning Label 77780294 Fuse Warning Label WARNING Do Not Replace Fuses While Energized ADVERTENCIA Desenergise Antes De Reemplazar Fusibles 77780388 Air Supply Label ENTRADA...

Page 216: ...LubriMist Oil Mist Generator has been designed and factory tested with LubriMist Synthetic Oil LSC recommends LSO for this oil mist generator in order to insure optimum performance IMPORTANT For refi...

Page 217: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 217 of 256 77780437 Aux Unit Start Up Instruction Sheet...

Page 218: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 218 of 256 77780434 Instruction Sheet Accessing The Alarm Event Log...

Page 219: ...ing and that the internal cabinet temperature is greater than 20 C while this equipment is energized See equipment operating instructions for further detail 77780475 ATEX Cabinet Cooling Option Label...

Page 220: ...rning Label WARNING Static Discharge Hazard Clean Plastic Surfaces With Damp Cloth Only 77780477 Warning Label 77780536 Heat Hot Surface Warning Label Sensitive Electronic Devices Caution Label CAUTIO...

Page 221: ...256 IVT Low Voltage Controller Layout THERMOCOUPLE I P TB1 TB2 TB3 TB4 TB10 TB5 TB6 TB7 TB9 TB8 4 20 MILLIAMP I P DIGITAL O P DIGITAL I P DISPLAY MAIN SYSTEM BOARD EC 1 15 14 FROM AC PANEL 24 VDC 34...

Page 222: ...ature Start Sensor H 3 Air Pre Heater TT H1 Air Oil Heater Main Oil Mist Generator H2 Air Oil Heater Auxiliary Oil Mist Generator H3 Air Pre Heater H4 Cabinet Heater w Thermostat Operator Access Compa...

Page 223: ...B TB1 BULK TANK OIL TEMP A O HTR HIGH AIR TEMP PRE HTR HIGH AIR TEMP TYPE K T C PRE HEATER AIR TEMP TYPE K T C TYPE K T C TYPE K T C FERRITE RED YELLOW SHIELD SHIELD RED YELLOW SHIELD RED YELLOW SHIEL...

Page 224: ...IST PRESSURE TRANSDUCER TRANSDUCER SUPPLY OIL PRES TRANSDUCER TB4 3 3 3 4 4 4 OUT OUT 5 5 5 OUT 4 20 SIGNAL OUT PT 2 4 20 SIGNAL OUT PT 3 4 20 SIGNAL OUT PT 4 4 20 SIGNAL OUT LT 1 WHITE RED 4 20 SIGNA...

Page 225: ...TION TANK LSL 1 BLACK LSL 2 LS 1 RED GREEN LS 2 WHITE LS LSL HIGH LEVEL SWITCH DEMISTING OIL RESERVOIR LSH 1 WHITE LSH 2 RED LSH INPUTS NOT USED AIR PRE HEATER RELAY STATUS LIGHT RELAY UY 1 7 R2 2 UY1...

Page 226: ...LD SHLD 2B 2A GND 15V SIG 5V 15V TB7 DETECTOR OIL MIST DENSITY RED WHITE GREEN BLACK BROWN FERRITE TB2 4 3 2 1 TB1 5 DI 1 D1 1 D1 2 D1 3 D1 4 D1 5 MIST MONITOR TEMPERATURE TRANSDUCER PRE HEATER START...

Page 227: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 227 of 256 IVT Controller Power Input Terminal 15 14 FROM AC PANEL 24 VDC GND TB9 24V GND GND...

Page 228: ...Mist Generating System Installation and Operating Manual Page 228 of 256 RS 422 485 Data Communication Terminal Strip TB8 R R X X 5V RX RX TX TX GND GND RX RX TX TX RS232 RS485 CUSTOMER INERFACE RS422...

Page 229: ...2 4 PSI NPT 27 2 MIST GENERATING KIT SIZE PER MIST CAPACITY 28 77780195 1 OIL MIST MONITOR DETECTOR ASSEMBLY 29 77780142 1 AMBIENT TEMPERATURE SENSOR RTD 100 OHM 30 77710711 1 DISPLAY 31 77710441 1 CO...

Page 230: ...230 of 256 General Arrangement Drawings IVT NEC Construction Operator Panel 10 11 OPERATOR INTERFACE FRONT 46 DETAIL A DETAIL D OIL TRANSFER PUMP MANUAL AIR VALVE 8 9 7 4 5 1 30 BULK OIL FILL PORT 8 9...

Page 231: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 231 of 256 Main Oil Mist Generator Access left door 17 2 12 15 45 LEFT SIDE MAIN ACCESS DETAIL G...

Page 232: ...l IVT Oil Mist Generating System Installation and Operating Manual Page 232 of 256 Auxiliary Oil Mist Generator Access right door RIGHT SIDE AUXILIARY ACCESS 027 26 DETAIL E DETAIL C 100 0 60 80 20 40...

Page 233: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 233 of 256 Top View DETAIL F 16 47 TOP VIEW 28 31 47 48 48...

Page 234: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 234 of 256 Electrical Power Switches...

Page 235: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 235 of 256 Oil Transfer Pump Oil Mist Discharge...

Page 236: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 236 of 256 Air Supply Components...

Page 237: ...age 237 of 256 Electrical Control Components AC PANEL COMPONENTS NEC 115VAC INCLUDED WITH AIR PREHEATER OPTION 38 49 43 AC PANEL COMPONENTS NEC 230VAC 32 38 34 38 38 33 52 43 42 38 43 49 38 32 34 33 3...

Page 238: ...VALVE 4 PSI NPT 27 2 MIST GENERATING KIT SIZE PER MIST CAPACITY 28 77780195 1 OIL MIST MONITOR DETECTOR ASSEMBLY 29 77780142 1 AMBIENT TEMPERATURE SENSOR RTD 100 OHM 30 77710711 1 DISPLAY 31 77780246...

Page 239: ...General Arrangement Drawings IVT ATEX Construction Operator Panel FRONT 11 10 BULK OIL FILL PORT 9 8 DETAIL A AUXILIARY RESERVOIR MANUAL OIL REFILL 2 4 5 DETAIL A DETAIL D DETAIL A STATUS LIGHT RED G...

Page 240: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 240 of 256 Main Oil Mist Generator Access left door LEFT SIDE MAIN ACCESS 17 2 12 DETAIL G 15 45 027...

Page 241: ...il Mist Generating System Installation and Operating Manual Page 241 of 256 Auxiliary Oil Mist Generator Access right door DETAIL B RIGHT SIDE AUXILIARY ACCESS 027 26 DETAIL E DETAIL C 100 0 60 80 20...

Page 242: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 242 of 256 Top View TOP VIEW 16 47 28 DETAIL F 48 48 47...

Page 243: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 243 of 256 Electrical Power Switches...

Page 244: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 244 of 256 Oil Transfer Pump Oil Mist Discharge...

Page 245: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 245 of 256 Air Supply Components...

Page 246: ...Operating Manual Page 246 of 256 Electrical Control Components AC PANEL COMPONENTS ATEX 115VAC INCLUDED WITH AIR PREHEATER OPTION 38 49 43 AC PANEL COMPONENTS ATEX 230VAC 32 38 34 38 38 33 51 52 43 42...

Page 247: ...1 TRANSDUCER TEMPERATURE PRE HEATER OPTION ONLY 2 77780179 77780180 77780181 77780182 1 AIR OIL HEATER ELEMENT 115 VAC 850 WATT ATEX CONSTRUCTION AIR OIL HEATER ELEMENT 230 VAC 850 WATT ATEX CONSTRUCT...

Page 248: ...Manual Page 248 of 256 Cold Ambient Option Cabinet heating NEC only ITEM PART NUMBER QUANTITY DESCRIPTION 1 77790181 or 77790182 2 CABINET HEATER 120 VAC 200 WATT CABINET HEATER 240 VAC 200 WATT 2 777...

Page 249: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 249 of 256 1 2 2 1 3 OPERATOR COMPARTMENT HEATER MECHANICAL COMPARTMENT HEATER REAR PANEL...

Page 250: ...nerating System Installation and Operating Manual Page 250 of 256 Cold Ambient Option Cabinet heating ATEX only ITEM PART NUMBER QUANTITY DESCRIPTION 1 77780442 2 CABINET HEATER 130 WATT w THERMOSTAT...

Page 251: ...Generating System Installation and Operating Manual Page 251 of 256 Air Purge Option ITEM PART NUMBER QUANTITY DESCRIPTION 1 51052525 1 PLUG VALVE 2 77700287 1 ROTOMETER INSTRUMENT AIR PURGE 3 7770028...

Page 252: ...d Operating Manual Page 252 of 256 Warm Ambient Option Cabinet Cooling NEC Construction ITEM PART NUMBER QUANTITY DESCRIPTION 1 77700320 1 BALL VALVE SS 2 77600542 1 AIR FILTER PRESSURE REGULATOR 3 77...

Page 253: ...Cooling ATEX Construction ITEM PART NUMBER QUANTITY DESCRIPTION 1 77780443 1 AIR PRESSURE REGULATOR 2 77780444 1 VORTEX COOLER 3 77780448 1 TEMPERATURE SWITCH 4 77780335 1 SOLENOID OPERATED AIR VALVE...

Page 254: ...SCRIPTION 1 77500843 1 OIL TRANSFER PUMP 2 77700501 1 AIR PRESSURE REGULATOR 3 77600088 1 GAUGE REGULATED AIR PRESSURE 4 1 VENT CAP 5 77780344 1 CHECK VALVE 10 PSI 6 77780198 1 HIGH LEVEL ALARM SWITCH...

Page 255: ...Page 255 of 256 Optional Auto Bulk Oil Fill ITEM PART NUMBER QUANTITY DESCRIPTION 1 77700321 1 BALL VALVE S S NPT 2 77780335 1 SOLENOID OIL VALVE 24VDC 3 77500487 1 OIL FILTER ELEMENT 10 MICRON SPIN O...

Page 256: ..._____________________________________________________ ________________________________________________________________ ________________________________________________________________ ________________...