CAUTION
• Metering media may be metered in excess.
• If the fl oat of the fl ow module gets stuck because of contaminations, the DULCOTROL
®
measuring/control station may meter in excess!
• Install a fi lter, depending on the type and composition of the sample water.
• If the circulating pump does not deliver, the DULCOTROL
®
measuring/control station
may meter in excess!
• Interlock the control via the potential-free contact of the circulating pump. If the cir cu-
lat ing pump is “OFF”, the DULCOTROL
®
measuring/control station goes to “PAUSE” via
the pause input of the controller.
• Alternatively, the metering pumps can be switched such that they only work together
with the circulating pumps.
5.1.1
Measuring
Station
The mounting height should be selected such that:
• the LCD panel of the control is well readable
• the cover of the controller can still be parked in “park position” (145 mm)
• there is still enough space below the in-line probe to carry out maintenance work (100 mm)
• there is enough space for the mounting of accessories beyond the panel
The following drilling dimensions are to be observed in accordance with the panel size:
Mounting/Installation
Number of measured variables 1
2
3
A 595
695
1000
B 745
695
800
C 555
655
960
D 705
655
760
BA_DR_002_02_09_GB_Cooling.indd 18