Page 58
Chlorine Dioxide Sensor CDP
Positive values of setting variable: chlorine dioxide
Negative values of setting variable: De-ClO
2
(chlorine dioxide
destruction)
auto.: 30.0
°
C
Permanent display 1
Permanent display 2
only with control
(w = setpoint)
Control with dead zone
For normal control
PID Control
Proportional control
Only with control
ppm
0.60
mea. val 0.60 ppm
feed fwd: 70 %
ctrl out: 59 %
w: 0.60 ppm
calibration ClO
2
zero p.: 4.00 mA
slope:
6.50 mA/ppm
calibration ClO
2
DPD-value:
0.60 ppm
temp.: 30.0
°
C
calibration ClO
2
zero p.: 4.00 mA
slope:
6.75 mA/ppm
limits
setting ?
control
setting ?
control
normal
control output
value: 30
%
set point
0.60 ppm
ctrl parameter
xp =
10 %
control
with dead zone
control output
value: 30
%
set point 2 upper
0.80 ppm
set point 1 lower
0.60 ppm
control
manual
control output
value: 30
%
manual dosing
15 %
regulated range
general setting
information
identcode: D1CA
DxDxxxxxxxxxx
software version
D1C-B1 FW-5.00
alarm relay
active
access c.: 5000
operating menu:
= english
= reduced
Access to setting menus
can be blocked
with access code.
Setting in
complete
operating
menu
For manual control
or
or
ctrl parameter
xp =
10 %
Ti =
off
Td =
off
limit 1
lower
0.10 ppm
limit 2
upper
1.50 ppm
Number and scope of
setting menus depends
on the device.
control
control output
positive ClO
2
negative De-ClO
2
D1C2-CIO2-010-GB
Restricted Operating Menu / Layout
The restricted operating menu permits simple operation of the most important parameters. The