Fault
Fault text
Symbol
Effect
Alarm with ack- Remarks
Remedy
on metering on control
nowledgement
Measured value
Checkout time
measured value exceeded
Check H
2
O
2
sensor
Basic load
Stop
Yes
Function defeatable
Check function of sensor,
extend check time
Signal exceeded/drops below
H
2
O
2
input < 3 mA
Basic load
Stop
Yes
Signal <3.0 ±0.2 mA
Check sensor, transducer and
value
H
2
O
2
input > 23 mA
or >23 ±0.2 mA
cable connection
Calibration sensor with error
calibration H
2
O
2
Basic load
Stop
No
Metering continues in
Check sensor,
not possible!
case of error with un-
replace if necessary,
steady measured values
recalibrate if necessary
Correction measured variable
Pt100-signal >138.5
Ω
Signal exceeded/drops below value
temp. input
yes
Signal <3.0 ±0.2 mA
Check sensor, transducer and
or >23 ±0.2 mA
cable connection
Value last valid is used
Feed forward control
Signal <3.8 ±0.2 mA
Check sensor, transducer
Signal drops below value multiplicative
feedfwd. < 4 mA
Stop
Yes
or >23 ±0.2 mA
and cable connection
additive
Value last valid is used
Signal exceeded
feedfwd. > 23 mA
Yes
Limit transgression
H
2
O
2
limit 1
Function defeatable
Defi ne cause, reset
after checkout time limit value
H
2
O
2
limit 2
values if necessary
Control “on”
Yes
Control “off”
Stop or
Stop
Yes
Basic load
Servomotor
Position not reached
Servomotor defective
Yes
Servomotor closes
Check servomotor
Electronics error
System error
Stop
Stop
Yes
Elektronic data defective
Call in service
8.3.3
DULCOMETER
®
D1C and DULCOTEST
®
PER Sensor for
Hydrogen Peroxide, Troubleshooting
Controller
H
2
O
2
Possible
values
Initial value
Increment
Lower value
Upper value
Remarks
Measured
0.01 %
-0.20 %
2.20 %
for measurement
value
range up to 2 %
0.01 %
-0.10 %
1.10 %
for measurement
range up to 1 %
1 ppm
-200 ppm
2200 ppm
for measurement
range up to 2000 ppm
0.1 ppm
-20.0 ppm
220.0 ppm
for measurement
range up to 200 ppm
0.01 ppm
-5.00 ppm
55.00 ppm
for measurement
range up to 50 ppm
0.01 ppm
-2.00 ppm
22.00 ppm
for measurement
range up to 20 ppm
Error message
Condition
Effect
Calibrate H
2
O
2
not possible!
H
2
O
2
slope too low
Calibrate again
Sensor slope too low
(<25 % of norm slope)
Calibrate H
2
O
2
not possible!
H
2
O
2
slope too high
Calibrate again
Sensor slope too high
(>300 % of norm slope)
H
2
O
2
value too low
H
2
O
2
<2 % measuring range
H
2
O
2
> x.xx ppm