pH/Chlorine
Operating Menu / Layout (Continuation)
relay
setting?
relay 1
meas. value 1 pH
relay 2
meas. value 2
chlorine
relay end
solenoid valve 2
- chlorine
period 10
s
min. time
1 s
solenoid valve 1
- acid
period
10 s
min. time
1 s
relay 1
relay adjustment
- limit
relay 2
relay adjustment
- limit
pumps
setting?
pumps
dosing direction
pump 1 acid
pump 2 chlorine
dosing pump max.
pump 1: 180
pump 2: 180
pulse/minute
setpoint
0.40 ppm
dosing direction:
chlorine
setpoint
7.20 pH
dosing direction:
acid
control
value 2 chlorine
control
end
control setting?
control
value 1 pH
control
automatic
dosing direction
acid
manual dosing
0 %
dosing direction:
acid
ctrl parameter
xp
= 10 %
Ti
= off
Td
= off
ctrl parameter
xp
= 10 %
Ti
= off
Td
= off
additional load:
0 %
dosing direction:
acid
control
automatic
dosing direction
chlorine
manual dosing
0 %
dosing direction:
chlorine
additional load:
0 %
dosing direction:
chlorine
limit
end
only with relay
hysteresis limit:
0.04 ppm
checkout time limit:
off
limit value
2 chlorine
limit relay: LV1
- active closed
Δ
t on
0 s
Δ
t off
0 s
limit 2
lower
0.60 ppm
limit 1
upper
0.10 ppm
limit 2
lower
0.60 ppm
limit 1
upper
0.10 ppm