Operation and installation manual
Page 74 of 82
(PVI-10.0/12.5-OUTD-xx Rev:1.2)
Description
Value
PVI – 10.0-OUTD-xx
Value
PVI – 12.5-OUTD-xx
Recommended
maximum DC power
11400 W
14300W
Nominal DC power
10400 W
13000 W
Nominal Input
Voltage
580 V
Max. DC Input
Voltage
850 Vdc
Max. Input
Overvoltage
900 Vdc for 2h/day
Input Voltage, MPPT
operatine range
200 Vdc to 850 Vdc
Input Voltage, MPPT
operating range at full
power
from 300 Vdc to 750
Vdc
from 360 Vdc to 750 Vdc
Max. short-circuit
current (of each array)
22 Adc
Max. operating input
current (of each array)
18 Adc
Max. input power (of
each channel)
(1)
6500 W
8000 W
PV ground fault
protection
Supplied ground fault detector and disconnect
Input channel
configuration
Two independent MPPT channels with shared negative
poles or
Two channels in parallel
(1)
Total input power shall in any case stay within recommended DC power value
NOTE
:
If photovoltaic field connected to the inverter outputs an input
current higher than the maximum one that can be used, the inverter will not
be damaged as far as the input voltage is within allowed range.