Operation and installation manual
Page 26 of 82
(PVI-10.0/12.5-OUTD-xx Rev:1.2)
Fig.9 - Connection diagram
WARNING
: When disconnecting AURORA from the grid, always open the
AC disconnect before the DC disconnect.
WARNING
: When selecting the power supply cables for AURORA
connection, please carefully consider nominal operating voltage, insulation
voltage, maximum operating temperature, current density and flammability
rating. All of these values must comply with the maximum current density
ratings required by applicable local rules.
A key consideration in cable selection is cable loss, as exceeding loss will
lead to derating.
For connection to the distribution grid, maximum cross-section of leads to be
mounted to terminal boards is 16 sq. mm for stiff cables and 10 sq. mm for
Bowden cables. Supplied M40 fairlead diameter is within the range 19mm –
28mm.