Operation and installation manual
Page 48 of 82
(PVI-10.0/12.5-OUTD-xx Rev:1.2)
3) Indicates the number of seconds left before completing the check on voltage and
frequency values measured at output.
As far as the Italian rules are concerned, maximum time for these checks is 20 seconds
while according to German standards it is 30 seconds.
4) Displays instant output voltage and gives information on whether this reading is
within the allowed range.
5) Displays instant output frequency and gives information on whether this reading is
within the allowed range.
6) If instant voltage reading -step 4)- and frequency reading -step 5)- are out of
allowed range, the display will cycle through the following pages
-
Next connections (page 3)
- Vgrid (page 4)
- Fgrid (page 5)
7) Instant value for insulation leakage
Meas. Riso
………………………
In range
Fout
50,17 Hz
In range
Vout
233,8 V
In range
Next connections:
2 secs