(PVI-10.0/12.5-OUTD-xx Rev:1.2)
5.5.7.7
Language
Set German or English.
5.5.7.8
START voltage
Start-up voltage can be set according to the photovoltaic field. Voltage range is 250V
to 500V. Aurora default setting is 360V. You can edit this parameter using the keys on
display.
Press ENTER to display the following page.
Select one of the two lines by pressing ENTER to set the start voltage for the two
channels, individually.
5.5.7.9
Alarm
The inverter features an alarm function that activates opening or closing of a relay
contact, access to this relay is ensured by opening the front panel as shown in Fig. 24.
For instance, this contact could be used to activate a siren or a visual alarm in case of
inverter disconnection from the grid (failed power output) or for any alarm event
generated by the system.
This function can trigger 2 different alarm modes. Press ENTER to open the
corresponding sub-menu:
VStart1
360V
Production
Fault
VStart1
VStart2
English
Deutsche