61
VersiStart i III
11.4
Auxiliary Trip Circuit
In normal operation the VersiStart i III is controlled via a remote two-wire signal (terminals 56, 57).
Input A (terminals 53, 55) is connected to an external trip circuit (such as a low pressure alarm switch for a pumping system). When the
external circuit activates, the soft starter trips, which stops the motor.
K1
F1
22
21
6/T3
2/T1
13
14
4/T2
24
33
34
5/L3
3/L2
S3
S1
S2
E
1/L1
65
64
41
40
56
57
58
53
55
A6
A5
A4
54
08880.
B
6
3
1
2
4
5
+
+
1
Three-phase supply
2
Motor terminals
3
Control voltage (model dependent)
4
Remote control inputs
5
Motor thermistor input
6
Relay outputs
S1 Start/stop
contact
S2 Reset
contact
S3
Auxiliary trip contact
13, 14
Relay output A (default = Main
Contactor)
21, 22, 24 Relay output B (default = Run)
33, 34
Relay output C (default = Trip)
53, 55
Programmable input A
(default = Motor Set Select)
Parameter settings:
x
Parameter 6D Input A Function
x
Select 'Input Trip (N/O)'. Assigns the Input A to Auxiliary Trip (N/O) function.
x
Parameter 6E Input A Name
x
Select a name, eg Low Pressure. Assigns a name to Input A.
x
Parameter 4E Input A Trip
x
Set as required. For example, 'Run Only' limits the input trip to when the soft starter is running only.
x
Parameter 5E Input A Trip Delay
x
Set as required. Sets a delay between the input activating and the soft starter tripping.
x
Parameter 5F Input A Initial Delay
x
Set at around 120 seconds. Limits operation of the input trip to 120 seconds after the start signal. This allows time for
pressure to build up in the piping before the low pressure input becomes active.