49
VersiStart i III
6E – Input A Name
Options:
Input Trip (default)
No Flow
Low Pressure
Starter Disable
High Pressure
Controller
Pump Fault
PLC
Low Level
Vibration
High Level
Description: Selects a message for the keypad to display when Input A is active.
9.4.7
7 Relay Outputs
7A – Relay A Function
Options:
Off
Relay A is not used.
Main Contactor (default)
The relay closes when the VersiStart i III receives a start command, and
remains closed as long as the motor is receiving voltage.
Run
The relay closes when the starter changes to run state.
Trip
The relay closes when the starter trips (refer to parameter 16A to 16M).
Warning
The relay closes when the starter issues a warning (refer to parameter 16A
to 16M).
Low Current Flag
The relay closes when the low current flag activates while the motor is
running (refer to parameter 7J Low Current Flag).
High Current Flag
The relay closes when the high current flag activates while the motor is
running (refer to parameter 7K High Current Flag).
Motor Temperature Flag
The relay closes when the motor temperature flag activates (refer to
parameter 7L Motor Temperature Flag).
Description: Selects the function of Relay A (normally open).
7B, 7C – Relay A Delays
The VersiStart i III can be configured to wait before opening or closing Relay A.
Parameter 7B Relay A On Delay
Range:
0:00 - 5:00 (minutes:seconds)
Default:
0 second
Description: Sets the delay for closing Relay A.
Parameter 7C Relay A Off Delay
Range:
0:00 - 5:00 (minutes:seconds)
Default:
0 second
Description: Sets the delay for re-opening Relay A.
7D~7I – Output Relays B & C
Parameters 7D~7I configure the operation of Relays B and C in the same way as parameters 7A~7C configure Relay A. Refer to Relay
A for details.
Relay B is a changeover relay.
x
7D Relay B Function
Default: Run
x
7E Relay B On Delay
x
7F Relay B Off Delay
Relay C is normally open.
x
7G Relay C Function
Default: Trip
x
7H Relay C On Delay
x
7I Relay C Off Delay
7J, 7K – Low Current Flag and High Current Flag
The VersiStart i III has low and high current flags to give early warning of abnormal operation. The current flags can be configured to
indicate an abnormal current level during operation, between the normal operating level and the undercurrent or instantaneous
overcurrent trip levels. The flags can signal the situation to external equipment via one of the programmable outputs.