59
VersiStart i III
11.2
Installation with Bypass Contactor
The VersiStart i III is installed with a bypass contactor (AC1 rated). The bypass contactor is controlled by the VersiStart i III Run Output
which by default is assigned to Output Relay B (terminals 21, 22, 24).
K1
22
21
13
14
24
33
34
E
6/T3
2/T1
4/T2
5/L3
3/L2
1/L1
L3B
L1B
L2B
K1
F1
65
64
41
40
56
57
58
53
55
A6
A5
A4
54
08878.
B
6
3
1
2
4
5
+
+
1
Three-phase supply
2
Motor terminals
3
Control voltage (model dependent)
4
Remote control inputs
5
Motor thermistor input
6
Relay outputs
K1
Bypass contactor (external)
F1
Semiconductor fuses (optional)
13, 14
Relay output A (default = Main Contactor)
21, 22, 24 Relay output B (default = Run)
33, 34
Relay output C (default = Trip)
53, 55
Programmable input A
(default = Motor Set Select)
Parameter settings:
x
Parameter 7D Relay B Function
x
Select 'Run' - assigns the run output function to Relay Output B (default value).