VersiStart i III
56
9.7
Setup Tools
Setup Tools includes maintenance options to configure the VersiStart i III's date and time, reset the thermal models or load a standard
parameter set.
To access the Setup Tools, open the Programming Menu then select Setup Tools.
9.7.1
Set Date and Time
To set the date and time:
1.
Open the Setup Tools.
2.
Scroll to the date/time screen.
3.
Press the button to enter edit mode.
4.
Press the and buttons to select which part of the date or time to edit.
5.
Use the
and
buttons to change the value.
6.
To save changes, press the button. The VersiStart i III will confirm the changes.
To cancel changes, press the button.
The Load/Save Settings menu requires an access code and allows users to:
x
Load the VersiStart i III's parameters with default values
x
Load parameter settings from an internal file
x
Save the current parameter settings to an internal file
In addition to the factory default values file, the VersiStart i III can store two user-defined parameter files. These files contain default
values until a user file is saved.
To load or save parameter settings:
1.
Open the Setup Tools.
2.
Scroll to Load/Save Settings and press the button.
3.
Scroll to the required function and press the button.
Load/Save Settings
Load
Defaults
Load User Set 1
Load User Set 2
4.
At the confirmation prompt, select YES to confirm or NO to cancel and then
MENU/ENTER
to load/save the selection.
Load
Defaults
No
Yes
When the action has been completed, the screen will briefly display a
confirmation message, then return to the status screens.
9.7.2
Reset Thermal Models
NOTE
This function is protected by the security access code.
The VersiStart i III's advanced thermal modelling software constantly monitors the motor's performance. This allows the VersiStart i III
to calculate the motor's temperature and ability to start successfully at any time. If the VersiStart i III is configured for use on two
motors, each motor's temperature is modelled separately.
The thermal model for the active motor can be reset if required.
1.
Open the Setup Tools.
2.
Scroll to Reset Thermal Models and press .
Reset Thermal Models
M1
X%
M2
X%
to Reset
3.
Use
to select Reset and press
MENU/ENTER
to confirm.
Do Not Reset
Reset
4.
When the thermal model has been reset, the screen will display a confirmation
message then return to the previous screen.
CAUTION
Resetting the motor thermal model will compromise thermal model protection and may compromise motor life. Only
reset the thermal model in an emergency.