5G – Frequency Delay
Range:
0:01 - 4:00 (minutes:seconds)
Default:
1 second
Description: Slows the VersiStart i III's response to frequency disturbances, avoiding trips due to momentary fluctuations.
9.4.6
6 Inputs
6A – Local/Remote
Options:
LCL/RMT Anytime
LOCAL/REMOTE
button is always enabled.
LCL/RMT When Off
LOCAL/REMOTE
button is enabled when the starter is off.
Local Control Only
All remote inputs are disabled.
Remote Control Only
Local control buttons (
START
,
RESET
,
LOCAL/REMOTE
) are
disabled.
Description: Selects when the
LOCAL/REMOTE
button can be used to switch between local and remote control, and enables or
disables the local control buttons and remote control inputs.
The
STOP
button on the keypad is always enabled.
6B – Comms in Remote
Options:
Disable Control in RMT
Enable Control in RMT (default)
Description: Selects whether the starter will accept Start and Stop commands from the serial communication network when in
Remote mode. The Reset and Local/Remote Control commands are always enabled.
6C – Remote Reset Logic
Options:
Normally Closed (default)
Normally Open
Description: Selects whether the VersiStart i III's remote reset input (terminals 58, 57) is normally open or normally closed.
6D – Input A Function
Options:
Motor Set Select (default)
The VersiStart i III can be configured with two separate sets of motor data.
To use the secondary motor data, parameter 6D must be set to 'Motor Set
Select' and 53, 55 must be closed when a start command is given. The
VersiStart i III checks which motor data to use at a start, and will use that motor
data for the entire start/stop cycle.
Input Trip (N/O)
Input A can be used to trip the soft starter. When parameter 6D is set to Input
Trip (N/O), a closed circuit across 53, 55 trips the soft starter.
Input Trip (N/C)
When parameter 6D is set to Input Trip (N/C), an open circuit across 53, 55
trips the soft starter.
Local/Remote Select
Input A can be used to select between local and remote control, instead of
using the
LOCAL/REMOTE
button on the keypad. When the input is open,
the starter is in local mode and can be controlled via the keypad. When the
input is closed, the starter is in remote mode. The
START
and
LOCAL/REMOTE
buttons are disabled, and the soft starter will ignore any
Local/Remote select command from the serial communications network.
To use Input A to select between local and remote control, parameter 6A must
be set to 'LCL/RMT Anytime' or 'LCL/RMT When Off'.
Emergency Run
In emergency run the soft starter continues to run until stopped, ignoring all
trips and warnings (refer to parameter 15C for details).
Closing the circuit across 53, 55 activates emergency run.
Opening the circuit ends emergency run and the VersiStart i III stops the
motor.
Starter Disable
The VersiStart i III can be disabled via the control inputs. An open circuit
across 53, 55 will disable the starter. The VersiStart i III will not respond to
start commands. If running, the soft starter will allow the motor to coast to
stop, ignoring the soft stop mode set in parameter 2H.
Jog Forward
Activates jog operation in a forward direction (will operate only in Remote
mode).
Jog Reverse
Activates jog operation in reverse direction (will operate only in Remote mode).
Description: Selects the function of Input A.