VersiStart i III
40
9.2
Standard Menu
The standard menu provides access to commonly used parameters, allowing the user to configure the VersiStart i III as required for the
application.
Default Setting
1
Motor Details
1A Motor Full Load Current Model
dependent
2
Primary Start/Stop
2A Start Mode Constant
Current
2B Current Limit 350%
2C Initial Current 350%
2D Start Ramp Time 00:10
mm:ss
2G Excess Start Time 00:20
mm:ss
2H Stop Mode
Coast To Stop
2I Stop Time 00:00
mm:ss
4
Protection Levels
4B Phase Sequence Any
Sequence
4C Undercurrent 20%
FLC
4D Instantaneous Overcurrent 400%
FLC
4E Input A Trip Always
Active
5
Protection Delays
5C Undercurrent Delay 00:05
mm:ss
5D Instantaneous Overcurrent Delay 00:00
mm:ss
5E Input A Trip Delay 00:00
mm:ss
5F Input A Initial Delay 00:00
mm:ss
6
Inputs
6D Input A Function
Motor Set Select
6E Input A Name Input
Trip
7
Relay Outputs
7A Relay A Function Main
Contactor
7B Relay A On Delay 00:00
mm:ss
7C Relay A Off Delay 00:00
mm:ss
7D Relay B Function Run
7E Relay B On Delay 00:00
mm:ss
7F Relay B Off Delay 00:00
mm:ss
7G Relay C Function Trip
7H Relay C On Delay 00:00
mm:ss
7I Relay C Off Delay 00:00
mm:ss
7J Low Current Flag 50%
FLC
7K High Current Flag 100%
FLC
7L Motor Temperature Flag 80%
FLC
10
Display
10A Language English
10B User Screen - Top Left Starter
State
10C User Screen - Top Right Blank
10D User Screen - Bottom Left Hours
Run
10E User Screen - Bottom Right Blank
10J Display A or kW Current