29
VersiStart i III
8.
Operation
8.1
The Keypad
O
C
I
Input A
Sta rt
Stop
Re se t
Ready
Run
Fault
Enter
Menu
Ex it
logs
Local
Remote
Rem ote Inputs
Local
5
1
2
3
4
6
1 Four-line display for status and programming details.
2
LOCAL/REMOTE
: Toggle between Local and Remote control
STATUS
: Open the status displays and scroll between different status
screens
GRAPHS
: Open the performance graphs and scroll between different
graph screens
LOGS
: Open the logs
3 Soft starter local control buttons:
START
: Start the motor
STOP
: Stop the motor
RESET
: Reset a trip (Local mode only).
4 Status LEDs (see below for details)
5 Menu navigation buttons:
EXIT
: Exit the menu or parameter, or cancel a parameter change.
: Enter a menu or parameter, or save a parameter change.
: Scroll to the next or previous menu or parameter, change the
setting of the current parameter or scroll through the status or graph
screens.
6 Remote input LEDs. When on:
INPUT A
: Programmable input A is active
START
: The remote start input is active
STOP
: The remote stop input is active
RESET
: The remote reset input is active
8.2
Starter Status LEDs
LED name
On
Flashing
Ready
The motor is stopped and the starter is ready to start.
The motor is stopped and the starter is waiting for the
Restart Delay (parameter 5A) or Motor Temperature
Check (parameter 4F).
Run
The motor is in run state (receiving full voltage).
The motor is starting or stopping.
Fault
The starter has tripped.
The starter is in warning state.
Local
The starter is in Local control mode.
–
Status
The status screens are active.
–
Graphs
The graph screens are active.
The graph has been paused.
Logs
The logs menu is open.
–
If the starter is in remote control mode, the Local LED will be off.
If all LEDs are off, the starter is not receiving control voltage.
8.3
Displays
The keypad displays a wide range of performance information about the soft starter. The top half of the screen shows real-time
information on current or motor power (as selected in parameter 10J). Use the
and
buttons to select the information shown on
the bottom half of the screen.
x
Starter status
x
Motor temperature
x
Current
x
Motor power
x
Last start information
x
Date and time
x
SCR conduction
NOTE
Screens shown here are with the default settings.