6.7
Power Terminations
NOTE
For personnel safety, the power terminals on models up to VS i III 105 are protected by snap-off tabs. When using large
cables, it may be necessary to break off these tabs.
NOTE
Some units use aluminium busbars. When connecting power terminations, we recommend cleaning the surface contact
area thoroughly (using an emery or stainless steel brush) and using an appropriate jointing compound to prevent corrosion.
Use only copper stranded or solid conductors, rated for 75 ºC or higher.
VS i III 23~VS i III 105
0
5
966.
E
Cable size:
6-50 mm
2
(AWG 10-1/0)
Torque: 4 Nm (2.9 ft-lb)
1129
0.
A
14 mm (0.55 inch)
Torx T20 x 150
Flat 7 mm x 150
VS i III 145
VS i III 170~VS i III 220
VS i III 255
19 Nm (14.0 ft-lb)
38 Nm (28.0 ft-lb)
38 Nm (28.0 ft-lb)
6 mm
19 mm
8.5 mm
(M8)
0
8
351.
B
0
8352.
B
6 mm
19 mm
10.5 mm
(M10)
5 mm
28 mm
11 mm
(M10)
13
181.
B
VS i III 350~VS i III 425
VS i III 500~VS i III 1000
VS i III 255N
38 Nm (28.0 ft-lb)
38 Nm (28.0 ft-lb)
38 Nm (28.0 ft-lb)
6 mm
28 mm
11 mm
(M10)
1
4543.
A
13 mm
32 mm
11 mm
(M10)
09866.
B
6 mm
32 mm
10.5 mm
(M10)
08353.
B
VS i III 360N~VS i III 930N
VS i III 1200N~VS i III 1600N
38 Nm (28.0 ft-lb)
66 Nm (48.7 ft-lb)
13 mm
32 mm
10.5 mm
(M10)
0835
4.
B
16 mm
51 mm
12.5 mm
(M12)
08355.
B