41
VersiStart i III
9.3
Extended Menu
The Extended Menu provides access to all the VersiStart i III's programmable parameters.
Default Setting
1
Motor Details
1A Motor Full Load Current Model
dependent
1B Locked Rotor Time 00:10
mm:ss
1C Motor FLC-2 Model
dependent
1D Locked Rotor Time-2 00:10
mm:ss
1E Dual Thermal Model Single
2
Primary Start/Stop
2A Start Mode Constant
Current
2B Current Limit 350%
FLC
2C Initial Current 350%
FLC
2D Start Ramp Time 00:10
mm:ss
2E Kickstart Level 500%
FLC
2F Kickstart Time 0
ms
2G Excess Start Time 00:20
mm:ss
2H Stop Mode
Coast To Stop
2I Stop Time 00:00
mm:ss
2J Adaptive Start Profile Constant
Acceleration
2K Adaptive Stop Profile Constant
Deceleration
2L Adaptive Control Gain 75%
3
Secondary Start/Stop
3A Start Mode-2 Constant
Current
3B Current Limit-2 350%
FLC
3C Initial Current-2 350%
FLC
3D Start Ramp-2 00:10
mm:ss
3E Kickstart Level-2 500%
FLC
3F Kickstart Time-2 0
ms
3G Excess Start Time-2 00:20
mm:ss
3H Stop Mode-2
Coast To Stop
3I Stop Time-2 00:00
mm:ss
3J Adaptive Start Profile-2 Constant
Acceleration
3K Adaptive Stop Profile-2 Constant
Deceleration
3L Adaptive Control Gain-2 75%
4
Protection Levels
4A Current Imbalance 30%
4B Phase Sequence Any
Sequence
4C Undercurrent 20%
FLC
4D Instantaneous Overcurrent 400%
FLC
4E Input A Trip Always
Active
4F Motor Temperature Check
Do Not Check
4G Frequency Check Start/Run
4H Frequency Variation ±5
Hz
5
Protection Delays
5A Restart Delay 00:10
mm:ss
5B Current Imbalance Delay 00:03
mm:ss
5C Undercurrent Delay 00:05
mm:ss
5D Instantaneous Overcurrent Delay 00:00
mm:ss
5E Input A Trip Delay 00:00
mm:ss
5F Input A Initial Delay 00:00
mm:ss
5G Frequency Delay 00:01
mm:ss
6
Inputs
6A Local/Remote LCL/RMT
Anytime
6B Comms in Remote
Enable Control in RMT
6C Remote Reset Logic
Normally Closed (N/C)
6D Input A Function
Motor Set Select
6E Input A Name Input
Trip