VersiStart i III
58
11.
Application Examples
A selection of Application Notes are available describing advanced installation or configuration of the VersiStart i III for situations with
specific performance requirements. Application notes are available for situations including brake and jog operation, pumping and
advanced protection options.
11.1
Installation with Main Contactor
The VersiStart i III is installed with a main contactor (AC3 rated). Control voltage must be supplied from the input side of the contactor.
The main contactor is controlled by the VersiStart i III Main Contactor output, which by default is assigned to Output Relay A (terminals
13, 14).
K1
K1
F1
22
21
6/T3
2/T1
13
14
4/T2
24
33
34
5/L3
3/L2
E
1/L1
65
64
41
40
56
57
58
53
55
A6
A5
A4
54
08877.
B
6
3
1
2
4
5
+
+
1
Three-phase supply
2
Motor terminals
3
Control voltage (model dependent)
4
Remote control inputs
5
Motor thermistor input
6
Relay outputs
K1 Main
contactor
F1
Semiconductor fuses (optional)
S1 Start/stop
contact
S2 Reset
contact
13, 14
Relay output A (default = Main Contactor)
21, 22, 24 Relay output B (default = Run)
33, 34
Relay output C (default = Trip)
53, 55
Programmable input A
(default = Motor Set Select)
Parameter settings:
x
Parameter 7A Relay A Function
x
Select 'Main Contactor' - assigns the Main Contactor function to Relay Output A (default setting)