27 

VersiStart i III 

 

Model 

SCR I

2

t (A

2

s) 

Supply Voltage 

< 440  VAC 

Supply Voltage 

< 575  VAC 

Supply Voltage 

< 690  VAC 

VS i III 430N 

320000 

AJT450 

AJT450 

 

VS i III 500 

320000 

AJT500 

AJT500 

 

VS i III 580 

781000 

A4BQ800 

A4BQ800 

 

VS i III 620N 

1200000 

A4BQ800 

A4BQ800 

 

VS i III 650N 

1200000 

A4BQ800 

A4BQ800 

 

VS i III 700 

781000 

A4BQ800 

A4BQ800 

 

VS i III 790N 

2530000 

A4BQ1200 

A4BQ1200 

 

VS i III 820 

1200000 

A4BQ1200 

A4BQ1200 

 

VS i III 920 

2530000 

A4BQ1200 

A4BQ1200 

 

VS i III 930N 

4500000 

A4BQ1200 / A4BT1100 

A4BQ1200 / A4BT1100 

 

VS i III 1000 

2530000 

A4BQ1200 

A4BQ1200 

 

VS i III 1200N 

4500000 

A4BQ1600 

A4BQ1600 

 

VS i III 1410N 

6480000 

A4BQ2000 

A4BQ2000 

 

VS i III 1600N 

12500000 

A4BQ2500 / A4BT1800 

A4BQ2500 / A4BT1800 

 

 

7.7.7

 

UL Fuse Selection and Short Circuit Ratings 

Two Short Circuit Current Ratings (SCCR) are available for UL compliant applications.   

x

 

Standard Fault Currents ( @ 600 VAC circuits)   

The standard fault currents are determined with reference to UL508, section 51, table 51.3. This specifies the short circuit current that 
the starter must withstand based upon the soft starter model horsepower rating (or Full Load Current (FLC) rating or Locked Rotor Amps 
(LRA) depending upon model).   

If using the Standard Fault Current Ratings, the fuse used must be in accordance with the information in the table below (i.e. model and 
manufacture specific).   

x

 

High Available Fault Currents ( @ 480 VAC circuits)   

It is possible to specify short circuit current ratings exceeding the minimum ratings set by the Standard Fault Currents (see above) when 
the soft starter is capable of withstanding the high available short circuit current in accordance with the UL 508 test.   

If using the High Available Fault Current Ratings, then a suitable fuse may be selected based upon Amperage and Fuse Class (J or L as 
applicable). 

 Model 

Nominal 

Rating (A) 

Short Circuit Ratings 

600 V Short 

cct rating –   

3 cycles † 

High Available 

Standard Fault Current 

@ 480 

VAC max. 

Max. Fuse 
Rating (A) 

(fuse class) 

@ 600 

VAC 

Ferraz/Mersen fuse, 

Listed J, L or RK5 Class 

Fuse 

Ferraz/Mersen fuse, R/C 

semi-conductor fuses   

VS i III 23 

23 

65 kA 

25 (J) 

10 kA 

AJT25 

A070URD30XXX0063 

Not available 

VS i III 43 

43 

65 kA 

50 (J) 

10kA 

AJT50 

A070URD30XXX0125 

VS i III 50 

50 

65 kA 

50 (J) 

10 kA 

AJT50 

A070URD30XXX0125 

VS i III 53 

53 

65 kA 

60 (J) 

10 kA 

AJT60 

A070URD30XXX0125 

VS i III 76 

76 

65 kA 

80 (J) 

10 kA 

AJT80 

A070URD30XXX0200 

VS i III 97 

97 

65 kA 

100 (J) 

10 kA 

AJT100 

A070URD30XXX0200 

VS i III 100 

100 

65 kA 

100 (J) 

10 kA 

AJT100 

A070URD30XXX0200 

VS i III 105 

105 

65 kA 

125 (J) 

10 kA 

AJT125 

A070URD30XXX0315 

VS i III 145 

145 

65 kA 

150 (J) 

18 kA 

AJT150 / RK5 200 

A070URD30XXX0315 

VS i III 170 

170 

65 kA 

175 (J) 

18 kA 

AJT175 / RK5 200 

A070URD30XXX0315 

VS i III 200 

200 

65 kA 

200 (J) 

18 kA 

AJT200 / RK5 300 

A070URD30XXX0450 

VS i III 220 

220 

65 kA 

250 (J) 

18 kA 

AJT250 / RK5 300 

A070URD30XXX0450 

VS i III 255 

255 

65 kA 

350 
(RK1/J) 

18 kA 

† 

18 kA – 
For 3 cycles 

VS i III 350 

350 

65 kA 

400 (J) 

18 kA 

† 

VS i III 425 

425 

65 kA 

450 (J) 

30 kA 

† 

A070URD33XXX0630 

30 kA – 
For 3 cycles 

VS i III 500 

500 

65 kA 

600 (J) 

30 kA 

600, Class J 

A070URD33XXX0700 

VS i III 580 

580 

65 kA 

800 (L) 

30 kA 

800, Class L 

VS i III 700 

700 

65 kA 

800 (L) 

42 kA 

800, Class L 

42 kA –   
For 3 cycles 

VS i III 820 

820 

65 kA 

1200 (L) 

42 kA 

1200, Class L 

A070URD33XXX1000 

VS i III 920 

920 

65 kA 

1200 (L) 

85 kA 

1200, Class L   

A070URD33XXX1400 

VS i III 1000 

1000 

65 kA 

1200 (L) 

85 kA 

1200, Class L 

A070URD33XXX1400 

 

 

Summary of Contents for VersiStart i III

Page 1: ...e l e c t r o n i c Quality is our Drive Commissioning Instructions VS i III 23 1600...

Page 2: ...ontrol Voltage 15 6 4 Control Wiring 15 6 5 Relay Outputs 15 6 6 Motor Thermistors 15 6 7 Power Terminations 16 6 8 Power Input and Output Configurations 17 6 9 Schematic Diagrams 18 7 Power Circuits...

Page 3: ...ontactor 58 11 2 Installation with Bypass Contactor 59 11 3 Emergency Run Operation 60 11 4 Auxiliary Trip Circuit 61 11 5 DC Brake with External Zero Speed Sensor 62 11 6 Soft Braking 63 11 7 Two Spe...

Page 4: ...to change at any time and without prior notice In no event will responsibility or liability be accepted for direct indirect or consequential damages resulting from the use or application of this equip...

Page 5: ...II to provide proper grounding and branch circuit protection according to local electrical safety codes 2 2 System Design and Safety of Personnel The starter is intended as a component for professiona...

Page 6: ...MENT D MARRAGES ACCIDENTELS Dans certaines installations des d marrages accidentels peuvent provoquer un risque suppl mentaire pour la s curit des personnes ou endommager les machines contr l es Dans...

Page 7: ...14 35 EU Low voltage directive is not proved The devices of the VersiStart i III series are electrical equipment that is used in industrial electrical power installations They are designed for applica...

Page 8: ...ing x Operational counters number of starts hours run kWh x Performance monitoring current voltage power factor kWh x User programmable monitoring screen Customisable protection x Motor overload x Exc...

Page 9: ...620 A 540 A 438 A VS i III 650N 650 A 650 A 561 A 455 A VS i III 700 700 A 592 A 512 A 438 A VS i III 790N 790 A 790 A 714 A 579 A VS i III 820 820 A 705 A 606 A 516 A VS i III 920 920 A 804 A 684 A 5...

Page 10: ...5 15 50 6 40 C 1000 metres AC53a 4 20 50 6 40 C 1000 metres AC53a 4 5 30 50 6 40 C 1000 metres VS i III 255N 255 A 222 A 195 A 171 A VS i III 360N 360 A 351 A 303 A 259 A VS i III 380N 380 A 380 A 348...

Page 11: ...A 124 A 930 A VS i III 650N 130 A 650 A 130 A 975 A VS i III 700 140 A 700 A 140 A 1050 A VS i III 790N 158 A 790 A 158 A 1185 A VS i III 820 164 A 820 A 164 A 1230 A VS i III 920 184 A 920 A 184 A 1...

Page 12: ...C Operating Altitude 0 1000 m above 1000 m with derating Humidity 5 to 95 Relative Humidity Pollution degree Pollution Degree 3 Vibration VS i III 23 VS i III 1000 IEC 60068 2 6 Heat Dissipation Duri...

Page 13: ...cabinet when terminating cables sized according to the National Wiring Code NEC regulations Terminal Connector Parts For models VS i III 145 VS i III 425 and VS i III 255N VS i III 1600N to be UL com...

Page 14: ...i III 220 32 2 VS i III 255 424 376 440 392 296 26 57 3 VS i III 350 16 7 14 8 17 3 15 4 11 7 29 4 VS i III 425 64 8 VS i III 500 49 VS i III 580 108 0 VS i III 700 433 320 640 600 293 62 5 VS i III...

Page 15: ...soft starter may be mounted on its side Derate the soft starter s rated current by 15 6 2 Control Terminals Control terminations use 2 5mm 2 plug in terminal blocks Unplug each block complete the wir...

Page 16: ...elow 120 of the programmed motor full load current and remains closed until the beginning of a stop either soft stop or coast to stop x If assigned to a trip function the output activates when a trip...

Page 17: ...C or higher VS i III 23 VS i III 105 05966 E Cable size 6 50 mm 2 AWG 10 1 0 Torque 4 Nm 2 9 ft lb 11290 A 14 mm 0 55 inch Torx T20 x 150 Flat 7 mm x 150 VS i III 145 VS i III 170 VS i III 220 VS i II...

Page 18: ...Enter Menu Local Remote Local Ready Run Trip Start Reset Stop Remote Inputs Input A Start Stop Reset StatusGraphs Logs Exit Enter Menu Local Remote Local Ready Run T rip Start Reset Stop Remote Inputs...

Page 19: ...model dependent 54 55 Start 2 Remote control inputs 56 57 Stop 3 Motor thermistor input 58 57 Reset 4 Relay outputs 53 55 Programmable input A default Motor Set Select 40 41 Analog output 13 14 Relay...

Page 20: ...g During this test the soft starter s control input and relay output protection settings can be tested This test mode is not suitable for testing soft starting or soft stopping performance The FLC of...

Page 21: ...Run refer to parameters 7A 7I K1 Main contactor optional K2 Bypass contactor external F1 Semiconductor fuses optional 13 14 Relay output A Main Contactor default 21 22 24 Relay output B Run default N...

Page 22: ...n when bypassed via an external bypass contactor The bypass contactor must be connected to the bypass terminals and controlled by a programmable output configured to Run refer to parameters 7A 7I M 3...

Page 23: ...full load current rating of the connected motor 7 4 Circuit Breaker A shunt trip circuit breaker may be used instead of a main contactor to isolate the motor circuit in the event of a soft starter tr...

Page 24: ...articular application 7 7 1 Bussman Fuses Square Body 170M Model SCR I 2 t A 2 s Supply Voltage 440 VAC Supply Voltage 575 VAC Supply Voltage 690 VAC VS i III 23 1150 170M1314 170M1314 170M1314 VS i I...

Page 25: ...00 320000 450FMM VS i III 580 781000 500FMM 500FMM 500FMM VS i III 620N 1200000 630FMM 630FMM VS i III 650N 1200000 630FMM 630FMM VS i III 700 781000 630FMM VS i III 790N 2530000 VS i III 820 1200000...

Page 26: ...URD30XXX0315 VS i III 145 125000 A070URD30XXX0315 A070URD30XXX0315 A070URD30XXX0315 VS i III 170 320000 A070URD30XXX0315 A070URD30XXX0315 A070URD30XXX0315 VS i III 200 320000 A070URD30XXX0450 A070URD3...

Page 27: ...0 6 9URD33D11A0700 VS i III 425 320000 6 9URD32D11A0630 VS i III 430N 320000 6 9URD33D11A0700 6 9URD33D11A0700 6 9URD33D11A0700 VS i III 500 320000 6 9URD32D11A0700 VS i III 580 781000 6 9URD32D11A080...

Page 28: ...high available short circuit current in accordance with the UL 508 test If using the High Available Fault Current Ratings then a suitable fuse may be selected based upon Amperage and Fuse Class J or L...

Page 29: ...AJT450 A070URD33XXX0700 VS i III 620N 620 65 kA 800 L 42 kA A4BQ800 A070URD33XXX1000 VS i III 650N 650 65 kA 800 L 42 kA A4BQ800 A070URD33XXX1000 VS i III 790N 790 65 kA 1200 L 42 kA A4BQ1200 A070URD3...

Page 30: ...input is active RESET The remote reset input is active 8 2 Starter Status LEDs LED name On Flashing Ready The motor is stopped and the starter is ready to start The motor is stopped and the starter i...

Page 31: ...phase Phase Currents 000 0A 000 0A 000 0A 8 3 5 Motor Power The motor power screen shows motor power kW HP and kVA and power factor 000 0kW 0000HP 0000kVA pf 8 3 6 Last Start Information The last star...

Page 32: ...mmunication network requires an optional communication module 8 4 1 Using the Soft Starter to Control a Motor To soft start the motor press the START button on the keypad or activate the Start remote...

Page 33: ...ct on line DOL start If the start ramp time parameter 2D is shorter than the motor s DOL start time starting current may reach DOL levels Every application has a particular starting profile based on c...

Page 34: ...aditional control methods Fine tuning Adaptive Control If the motor does not start or stop smoothly adjust the adaptive control gain parameter 2L The gain setting determines how much the VersiStart i...

Page 35: ...t supplies Voltage full voltage 1 1 Stop Time parameter 2I Time 8 6 3 Adaptive Control for Stopping In an adaptive control soft stop the VersiStart i III controls the current in order to stop the moto...

Page 36: ...profile and stop time If replacing a motor connected to a VersiStart i III programmed for Adaptive Control starting or stopping or if the starter has been tested on a different motor prior to actual i...

Page 37: ...on using the VersiStart i III with an external speed sensor eg for applications with variable load during the braking cycle refer to DC Brake with External Zero Speed Sensor on page 62 8 7 Jog Operat...

Page 38: ...R soft stop if parameter 2I Stop Time is 0 secs If parameter 2I is set to 0 secs the starter performs a coast to stop Jog The starter issues a warning with the error message Unsupported Option Brake T...

Page 39: ...conds the value will increase or decrease at a faster rate x to save changes press STORE The setting shown on the display will be saved and the keypad will return to the parameter list x to cancel cha...

Page 40: ...rly Acceleration 5 seconds Adaptive Control Late Deceleration 5 seconds Fan Damped Motor Full Load Current Start Mode Current Limit Model dependent Constant Current 350 Fan Undamped Motor Full Load Cu...

Page 41: ...on Delays 5C Undercurrent Delay 00 05 mm ss 5D Instantaneous Overcurrent Delay 00 00 mm ss 5E Input A Trip Delay 00 00 mm ss 5F Input A Initial Delay 00 00 mm ss 6 Inputs 6D Input A Function Motor Set...

Page 42: ...0 FLC 3D Start Ramp 2 00 10 mm ss 3E Kickstart Level 2 500 FLC 3F Kickstart Time 2 0 ms 3G Excess Start Time 2 00 20 mm ss 3H Stop Mode 2 Coast To Stop 3I Stop Time 2 00 00 mm ss 3J Adaptive Start Pro...

Page 43: ...ight Blank 10D User Screen Bottom Left Hours Run 10E User Screen Bottom Right Blank 10F Graph Timebase 10 seconds 10G Graph Maximum Adjustment 400 10H Graph Minimum Adjustment 0 10I Mains Reference Vo...

Page 44: ...nt from cold before reaching its maximum temperature Set according to the motor datasheet 1E Dual Thermal Model Options Single default Dual Description Activates dual thermal modelling The dual therma...

Page 45: ...tly longer than required for a normal healthy start A setting of 0 disables excess start time protection Range 0 00 4 00 minutes seconds Default 20 seconds Description Set as required 2H Stop Mode Opt...

Page 46: ...motor full load current 3C Initial Current 2 Range 100 600 Default 350 Description Sets the initial start current level for current ramp starting as a percentage of motor full load current Set so that...

Page 47: ...tive Only Description Selects which phase sequences the soft starter will allow at a start During its pre start checks the starter examines the sequence of the phases at its input terminals and trips...

Page 48: ...uring the restart delay period the display shows the time remaining before another start can be attempted 5B Current Imbalance Delay Range 0 00 4 00 minutes seconds Default 3 seconds Description Slows...

Page 49: ...use at a start and will use that motor data for the entire start stop cycle Input Trip N O Input A can be used to trip the soft starter When parameter 6D is set to Input Trip N O a closed circuit acr...

Page 50: ...er to parameter 7L Motor Temperature Flag Description Selects the function of Relay A normally open 7B 7C Relay A Delays The VersiStart i III can be configured to wait before opening or closing Relay...

Page 51: ...sociated equipment to monitor motor performance 8A Analog Output A Options Current FLC default Current as a percentage of motor full load current Motor Temp Motor temperature as a percentage of the mo...

Page 52: ...uto reset the VersiStart i III will restart 9A Auto Reset Action Options Do Not Auto Reset default Reset Group A Reset Group A B Reset Group A B C Description Selects which trips can be auto reset 9B...

Page 53: ...or has run via the soft starter Description Selects which information will be displayed on the programmable monitoring screen x 10B User Screen Top Left Default Starter State x 10C User Screen Top Rig...

Page 54: ...Run Options Disable default Enable Description Selects whether the soft starter will permit emergency run operation In emergency run the soft starter will start if not already running and continue to...

Page 55: ...rter will trip on Lx Tx Shorted on the first start attempt after control power is applied PowerThrough will not operate if control power is cycled between starts PowerThrough operation does not suppor...

Page 56: ...the Extended Menu 3 Select Restricted 4 Enter the Access Code 5 Select parameter 15B Adjustment Lock 6 Select and store Read Only If a user attempts to change a parameter value when the adjustment lo...

Page 57: ...and press the button 3 Scroll to the required function and press the button Load Save Settings Load Defaults Load User Set 1 Load User Set 2 4 At the confirmation prompt select YES to confirm or NO to...

Page 58: ...of the starter s 99 most recent events actions warnings and trips including the date and time of the event Event 1 is the most recent and event 99 is the oldest stored event To open the Event Log 1 O...

Page 59: ...siStart i III Main Contactor output which by default is assigned to Output Relay A terminals 13 14 K1 K1 F1 22 21 6 T3 2 T1 13 14 4 T2 24 33 34 5 L3 3 L2 E 1 L1 65 64 41 40 56 57 58 53 55 A6 A5 A4 54...

Page 60: ...1 40 56 57 58 53 55 A6 A5 A4 54 08878 B 6 3 1 2 4 5 1 Three phase supply 2 Motor terminals 3 Control voltage model dependent 4 Remote control inputs 5 Motor thermistor input 6 Relay outputs K1 Bypass...

Page 61: ...ependent 4 Remote control inputs 5 Motor thermistor input 6 Relay outputs S1 Start stop contact S2 Reset contact S3 Emergency Run Contact 13 14 Relay output A default Main Contactor 21 22 24 Relay out...

Page 62: ...tact 13 14 Relay output A default Main Contactor 21 22 24 Relay output B default Run 33 34 Relay output C default Trip 53 55 Programmable input A default Motor Set Select Parameter settings x Paramete...

Page 63: ...will open and the starter will be disabled When the next start command is given ie next application of K10 53 55 closes and the VersiStart i III is enabled The VersiStart i III must be operated in re...

Page 64: ...ntrol voltage model dependent A2 Zero speed sensor 2 Remote control inputs K10 Run relay 3 Motor thermistor input K11 Start relay 4 Relay outputs K12 Brake relay 5 Three phase supply K13 Zero speed se...

Page 65: ...K10 K11 K3 K10 K2 K11 K1 K2 K3 K1 K3 K1 K3 K2 S1 K2 K1 K10 56 57 58 53 55 54 1 Control voltage model dependent K10 Remote start relay low speed 2 Remote control inputs K11 Remote start relay high spe...

Page 66: ...tery the main control PCB must be replaced Related parameters 16K Controller This is a name selected for a programmable input Refer to Input A trip Current imbalance Current imbalance can be caused by...

Page 67: ...the affected phase has dropped below 2 of the programmed motor FLC for more than 1 second indicating that either the incoming phase or connection to the motor has been lost Check the supply and the i...

Page 68: ...ins supply on one or more phases when a Start Command is given Check that the main contactor closes when a start command is given and remains closed until the end of a soft stop Check the fuses If tes...

Page 69: ...ol before attempting another start x The starter may be disabled via a programmable input If parameter 6D is set to Starter Disable and there is an open circuit on 53 55 the VersiStart i III will not...

Page 70: ...so that the starter can learn from the motor characteristics Subsequent starts use Adaptive Control PowerThrough does not operate when selected x The starter will trip on Lx Tx Shorted on the first st...

Page 71: ...either the remote keypad or the keypad on the starter Both displays show the same information The remote keypad also allows parameter settings to be copied between soft starters 13 3 Finger Guard Kit...

Page 72: ...iring loom with the number of the corresponding terminal on the backplane PCB then unplug the looms 8 Unplug the thermistor fan and current transformer wires from the model board 9 Remove the plastic...

Page 73: ...f the starter Remove the cable ties and unscrew the CTs from the bracket 2 Move the CT bracket to the top of the starter Position the CTs for the correct phases then screw the CTs to the bracket For m...

Page 74: ...73 VersiStart i III...

Page 75: ...Phone ax eMail 49 0 49 0 9189 4147 0 9189 4147 47 mail peter electronic com F PETER electronic GmbH Co KG Bruck cker 9 D 92348 Berg www peter electronic com...

Reviews: