VersiStart i III
60
11.3
Emergency Run Operation
In normal operation the VersiStart i III is controlled via a remote two-wire signal (terminals 56, 57).
Emergency Run is controlled by a two-wire circuit connected to Input A (terminals 53, 55). Closing Input A causes the VersiStart i III to
run the motor and ignore certain trip conditions.
K1
F1
22
21
6/T3
2/T1
13
14
4/T2
24
33
34
5/L3
3/L2
S3
S1
S2
E
1/L1
65
64
41
40
56
57
58
53
55
A6
A5
A4
54
08879.
B
6
3
1
2
4
5
+
+
1
Three-phase supply
2
Motor terminals
3
Control voltage (model dependent)
4
Remote control inputs
5
Motor thermistor input
6
Relay outputs
S1 Start/stop
contact
S2 Reset
contact
S3
Emergency Run Contact
13, 14
Relay output A (default = Main
Contactor)
21, 22, 24 Relay output B (default = Run)
33, 34
Relay output C (default = Trip)
53, 55
Programmable input A
(default = Motor Set Select)
Parameter settings:
x
Parameter 6D Input A Function
x
Select 'Emergency Run' - assigns Input A for Emergency Run function.
x
Parameter 15C Emergency Run
x
Select 'Enable' - Enables Emergency Run mode.
NOTE
Although the Emergency Run satisfies the functionality requirements of Fire Mode, Peter Electronic does not
recommend its use in situations that require testing and/or compliance with specific standards as it is not certified.