45
VersiStart i III
2L – Adaptive Control Gain
Range:
1% - 200%
Default:
75%
Description: Adjusts the performance of Adaptive Control. This setting affects both starting and stopping control.
NOTE
We recommend leaving the gain setting at the default level unless performance is not satisfactory.
If the motor accelerates or decelerates too quickly at the end of a start or stop, increase the gain setting by 5%~10%. If
the motor speed fluctuates during starting or stopping, decrease the gain setting slightly.
9.4.3
3 Secondary Start/Stop
Refer to the Primary Start/Stop parameters for parameter details.
3A – Start Mode-2
Options:
Constant Current (default)
Adaptive Control
Description: Selects the soft start mode.
3B – Current Limit-2
Range:
100% - 600% FLC
Default:
350%
Description: Sets the current limit for constant current and current ramp soft starting, as a percentage of motor full load current.
3C – Initial Current-2
Range: 100%
-
600%
Default:
350%
Description: Sets the initial start current level for current ramp starting, as a percentage of motor full load current. Set so that the
motor begins to accelerate immediately after a start is initiated.
If current ramp starting is not required, set the initial current equal to the current limit.
3D – Start Ramp Time-2
Range:
1 - 180 (seconds)
Default:
10 seconds
Description: Sets the total start time for an Adaptive Control start or the ramp time for current ramp starting (from the initial current to
the current limit).
3E – Kickstart Level-2
Range:
100% - 700% FLC
Default:
500%
Description: Sets the level of the kickstart current.
3F – Kickstart Time-2
Range:
0 - 2000 (milliseconds)
Default:
0000 milliseconds
Description: Sets the kickstart duration. A setting of 0 disables kickstart.
3G – Excess Start Time-2
Range:
0:00 - 4:00 (minutes:seconds)
Default:
20 seconds
Description: Set as required.
3H – Stop Mode-2
Options:
Coast To Stop (default)
TVR Soft Stop
Adaptive Control
Brake
Description: Selects the stop mode.